CL-4
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
ITEM EXPANSION RANGE DEFAULT ENTRY
DEHU DEHUMIDIFICATION CONFIG.
D.SEL Dehumidification Config 0-2(multi-text strings) 0
D.SEN Dehumidification Sensor 1-2(multi-text strings) 1
D.EC.D Econ disable in DH mode? Yes/No Yes
D.V.CF Vent Reheat Setpt Select 0-1(multi-text strings) 0
D.V.RA Vent Reheat RAT offset 0-8 ^F 0
D.V.HT Vent Reheat Setpoint 55-95 dF 70
D.C.SP Dehumidify Cool Setpoint 40-55 dF 45
D.RH.S Dehumidify RH Setpoint 10-90 % 55
CCN CCN CONFIGURATION
CCNA CCN Address 1 - 239 1
CCNB CCN Bus Number 0 - 239 0
BAUD CCN Baud Rate 1 - 5 (multi-text strings) 3
BROD CCN BROADCST DEFINITIONS
BROD
TM.DT CCN Time/Date Broadcast ON/OFF On
BROD
OAT.B CCN OAT Broadcast ON/OFF Off
BROD
ORH.B CCN OARH Broadcast ON/OFF Off
BROD
OAQ.B CCN OAQ Broadcast ON/OFF Off
BROD
G.S.B Global Schedule Broadcst ON/OFF Off
BROD
B.ACK CCN Broadcast Ack'er ON/OFF Off
SC.OV CCN SCHEDULES-OVERRIDES
SC.OV
SCH.N Schedule Number 0 - 99 1
SC.OV
HOL.T Accept Global Holidays? YES/NO No
SC.OV
O.T.L. Override Time Limit 0 - 4 HRS 1
SC.OV
OV.EX Timed Override Hours 0 - 4 HRS 0
SC.OV
SPT.O SPT Override Enabled ? YES/NO Yes
SC.OV
T58.O T58 Override Enabled ? YES/NO Yes
SC.OV
GL.OV Global Sched. Override ? YES/NO No
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ –10-245 dF 60
SP.H.O SPT hi alert limit/occ –10-245 dF 85
SP.L.U SPT lo alert limit/unocc –10-245 dF 45
SP.H.U SPT hi alert limit/unocc –10-245 dF 100
SA.L.O EDT lo alert limit/occ –40-245 dF 40
SA.H.O EDT hi alert limit/occ –40-245 dF 100
SA.L.U EDT lo alert limit/unocc –40-245 dF 40
SA.H.U EDT hi alert limit/unocc –40-245 dF 100
RA.L.O RAT lo alert limit/occ –40-245 dF 60
RA.H.O RAT hi alert limit/occ –40-245 dF 90
RA.L.U RAT lo alert limit/unocc –40-245 dF 40
RA.H.U RAT hi alert limit/unocc –40-245 dF 100
R.RH.L RARH low alert limit 0-100 % 0
R.RH.H RARH high alert limit 0-100 % 100
SP.L SP low alert limit 0-5 "H2O 0
SP.H SP high alert limit 0-5 "H2O 2
BP.L BP lo alert limit –0.25-0.25 "H2O -0.25
BP.H BP high alert limit –0.25-0.25 "H2O 0.25
IAQ.H IAQ high alert limit 0-5000 1200
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim –10 - 10 ^F 0
RAT.T RAT Trim –10 - 10 ^F 0
OAT.T OAT Trim –10 - 10 ^F 0
SPT.T SPT Trim –10 - 10 ^F 0
CTA.T Cir A Sat.Cond.Temp Trim –30 - 30 ^F 0
CTB.T Cir B Sat.Cond.Temp Trim –30 - 30 ^F 0
SP.A.T Suct.Press.Circ.A Trim –50 - 50 PSIG 0
SP.B.T Suct.Press.Circ.B Trim –50 - 50 PSIG 0
DP.A.T Dis.Press.Circ.A Trim –50 - 50 PSIG 0
DP.B.T Dis.Press.Circ.B Trim –50 - 50 PSIG 0
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close Open
IGC.L IGC Feedback - Off Open/Close Open
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close Open
ECS.L Economizer Switch - No Open/Close Open
SFS.L Fan Status Sw. - Off Open/Close Open
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close Open
DL2.L Dmd.Lmt.-Dehumid - Off Open/Close Open
IAQ.L IAQ Disc.Input - Low Open/Close Open
FSD.L Fire Shutdown - Off Open/Close Open
PRS.L Pressurization Sw. - Off Open/Close Open
EVC.L Evacuation Sw. - Off Open/Close Open
PRG.L Smoke Purge Sw. - Off Open/Close Open
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF Off
METR Metric Display ON/OFF Off
LANG Language Selection 0-1(multi-text strings) 0
PAS .E Password Enable ENABLE/DISABLE Enable
PAS S Service Password 0000-9999 1111