17
Fig. 15 — Base Unit Dimensions — 48EW,EY038-048
NOTES:
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing econo-
mizer inlet.
Min Clearances to be:
Adjacent Units: 15-0 [4572].
Top of Units: No Overhang.
Condenser Coil: 4-0 [1219].
Economizer Side: 6-0 [1829].
Heat Side: 4-0 [1219].
Filter Access Side: 15-0 [4572]. (For removal of evaporator
coil.)
4. For smaller service and operational clearances contact Carrier
Application Engineering Department.
5. Dimensions in are in inches [mm].