62
operation, this will be the MSAS (supply-air set point + reset)
for cooling and the heating set point for heating.
Press to display the control temperature. This display is
the actual supply-air temperature leaving the unit.
(Temperature) — The system temperature subfunc-
tion displays the readings at the temperature sensing ther-
mistors. To read a temperature, press , then scroll to the
desired temperature reading by pressing .
(Pressure) — The system pressure subfunction dis-
plays suction, discharge, low-pressure switch status, building
pressure, and static pressure.
(Inputs) — This subfunction displays the rest of the
system inputs. Press , then press . The compres-
sor A1 status is displayed with either ON or OFF based on
whether the compressor is running or not. Press to access
additional system inputs. Some inputs can be used forced by
entering a value to replace the actual value. For example, press
until the ENT display appears. The display will show ENT
LOW or ENT HGH, indicating that the enthalpy is good
(LOW) or bad (HGH).
Table 54 — Status Directory
See legend and notes on page 67.
STATUS
Subfunction Keypad Entry Display Expansion (Press key)
1 ALARMS
ALARMS CURRENT ALARMS
ALARM 51 COMPRESSOR A1 FAULT
ALARM 52 COMPRESOR A2 FAULT (Sizes 088, 104 Only)
ALARM 53 COMPRESSOR A1 STATUS
ALARM 55 COMPRESSOR B1 FAULT
ALARM 56 COMPRESSOR B2 FAULT (Sizes 088,104 Only)
ALARM 57 COMPRESSOR B1 STATUS
ALARM 59 THERMISTOR FAILURE SUPPLY AIR
ALARM 60 THERMISTOR FAILURE RETURN AIR
ALARM 61 OUTSIDE AIR THERMISTOR FAILURE
ALARM 62 CIRCUIT A CONDENSER THERMISTOR FAILURE
ALARM 63 CIRCUIT B CONDENSER THERMISTOR FAILURE
ALARM 64 COMPRESSOR A1 THERMISTOR FAILURE
ALARM 65 COMPRESSOR B1 THERMISTOR FAILURE
ALARM 66 SPACE THERMISTOR FAILURE
ALARM 67 CIRCUIT A DISCHARGE TRANSDUCER FAILURE
ALARM 68 CIRCUIT B DISCHARGE TRANSDUCER FAILURE
ALARM 69 CIRCUIT A SUCTION TRANSDUCER FAILURE
ALARM 70 CIRCUIT B SUCTION TRANSDUCER FAILURE
ALARM 71 LOSS OF COMMUNICATION WITH DSIO1
ALARM 72 LOSS OF COMMUNICATION WITH DSIO2
ALARM 73 LOSS OF COMMUNICATION WITH OPTION BOARD 1 (PSIO2)
ALARM 74 LOW PRESSURE CIRCUIT A
ALARM 75 LOW PRESSURE CIRCUIT B
ALARM 76 HIGH PRESSURE CIRCUIT A
ALARM 77 HIGH PRESSURE CIRCUIT B
ALARM 78 SUPPLY FAN FAILURE
ALARM 80 LOW CIRCUIT A SATURATED SUCTION TEMP
ALARM 81 LOW CIRCUIT B SATURATED SUCTION TEMP
ALARM 82 HIGH CIRCUIT A SUCTION SUPERHEAT
ALARM 83 HIGH CIRCUIT B SUCTION SUPERHEAT