64
Table 54 — Status Directory (cont)
See legend and notes on page 67.
STATUS (cont)
Subfunction Keypad Entry Display Expansion (Press key)
3 MODES (cont) MODE 27 MODE IS UNOCCUPIED
MODE 28 MODE IS IAQ PURGE
MODE 29 MODE IS OPTIMAL STOP
MODE 30 MODE IS OCCUPIED HEAT
MODE 31 MODE IS OCCUPIED COOL
MODE 32 MODE IS OCCUPIED
MODE 33 MODE IS NIGHT TIME FREE COOL
MODE 34 MODE IS PRESSURIZATION
MODE 35 MODE IS EVACUATION
MODE 36 MODE IS SMOKE PURGE
MODE 37 MODE IS FIRE SHUTDOWN
MODE 38 MODE IS TIMED OVERRIDE
MODE 39 MODE IS DAV CONTROL
MODE 40 MODE IS FACTORY-FIELD TEST
MODE 41 MODE IS HIGH HUMIDITY OVERRIDE
MODE 42 MODE IS IAQ/OAC CONTROL (Sizes 088,104 Only)
4 STAGES
STAGES CURRENT STAGES
COOL X COOLING STAGES X
CPC X COOLING PERCENT CAPACITY X
HEAT X HEATING STAGES X
HPC X HEATING PERCENT CAPACITY X
SMZ X SUM/Z RATIO X
5 SET POINT
SETPOINT CURRENT OPERATING SETPOINT
CLSP X CONTROL SETPOINT X
CLTP X CONTROL TEMP X
6 TEMPERATURE
TEMPS SYSTEM TEMPERATURES
SCTA X CIRCUIT A SATURATED CONDENSING TEMP X
STA X CIRCUIT A SUCTION TEMP X
SSTA X CIRCUIT A SATURATED SUCTION TEMP X
SHA X CIRCUIT A SUCTION SUPERHEAT
SCTB X CIRCUIT B SATURATED CONDENSING TEMP X
STB X CIRCUIT B SUCTION TEMP X
SSTB X CIRCUIT B SATURATED SUCTION TEMP X
SHB X CIRCUIT B SUCTION SUPERHEAT
SAT X SUPPLY AIR TEMP X
RAT X RETURN AIR TEMP X