65
Table 54 — Status Directory (cont)
STATUS (cont)
Subfunction Keypad Entry Display Expansion (Press key)
6 TEMPERATURE (cont)
SPT X SPACE TEMP X
OAT X OUTSIDE AIR TEMP X
X *
OAT X OUTSIDE AIR TEMP X (–40 F to 245 F)
7 PRESSURE
PRESSURE SYSTEM PRESSURES
DPA X
CIRCUIT A DISCHARGE PRESSURE SENSOR X
SPA X CIRCUIT A SUCTION PRESSURE SENSOR X
LPA X CIRCUIT A LOW PRESSURE SWITCH X
DPB X CIRCUIT B DISCHARGE PRESSURE SENSOR X
SPB X CIRCUIT B SUCTION PRESSURE SENSOR X
LPB X CIRCUIT B LOW PRESSURE SWITCH X
BP X BUILDING PRESSURE X
SP X STATIC PRESSURE X
8 INPUTS
INPUTS SYSTEM INPUTS
CSA1 X COMPRESSOR A1 STATUS X
CSB1 X COMPRESSOR B1 STATUS X
CFA1 X COMPRESSOR A1 SAFETY X
CFB1 X COMPRESSOR B1 SAFETY X
CFA2 X COMPRESSOR A2 SAFETY X (Sizes 088 and 104 Only)
CFB2 X COMPRESSOR B2 SAFETY X (Sizes 088 and 104 Only)
OAC X OUTSIDE AIR CFM X
IAQ X INDOOR AIR QUALITY X
SFS X SUPPLY FAN STATUS X
ENT X ENTHALPY SWITCH X
X*
ENT X ENTHALPY SWITCH X (0 = High, 1 = Low)
RH X RELATIVE HUMIDITY X
X*
RH X RELATIVE HUMIDITY X (0 to 100%)
FRZ X FREEZE STAT X
OARH X OUTSIDE AIR RELATIVE HUMIDITY X
X*
OARH X OUTSIDE AIR RELATIVE HUMIDITY X (0 to 100%)
FLTS X FILTER STATUS X
X*
FLTS X FILTER STATUS X (0 = Clean, 1 = Dirty)
STO X SPACE TEMP OFFSET X
EVAC X EVACUATION X
PRES X PRESSURIZATION X
PURG X SMOKE PURGE X
FSD X FIRE SHUTDOWN X
9 ANALOG
ANALOG ANALOG OUTPUTS
IGV X INLET GUIDE VANES X (Sizes 034-078)†