FIOP Smoke Detector Wiring and Response
All units: FIOP smoke detector is configured to
automatically shut down all unit operat ions when a smoke
condition is detected. See Fig. 41, Smoke Detector
Wiring.
Highlight A: JMP 3 is factory--cut, transferring unit
control to smoke detector.
Highlight B: Smoke detector NC contact set will open on
smoke alarm conditi on, de--energizing the ORN
conduct or.
Highlight C: 24V power signal using the ORN lead is
remove d at the Smoke Detector input on LCTB; all unit
operations cease immediately.
PremierLink and RTU--OPEN Controls: Unit
operating functions (fan, cooling and heating) are
terminated as described above. In addition:
Highlight D: On smoke alarm conditi on, the smoke
dete ctor NO Alarm contact will close, supplying 24--v
power to GRA conductor.
Highlight E: GRA lead at Smoke Alarm input on LCTB
provides 24--v signal to FIOP DDC control.
Premier--Link: This signal is c onveyed to PremierLink
FIOP’s TB1 at terminal TB1--6 (BLU lead). This signal
initiates the FSD sequence by the PremierLink control.
FSD status is reported to connect ed CCN network.
RTU--OPEN: The 24--v signal is conveyed to
RT U--OPEN -- J1--10 input terminal. This signal i nitiates
the FSD sequence by the RTU--OPEN c ontrol. FSD status
is reported to connected BAS network.
Using Remote Logic : Five conductors are provided for
field use (see Highlight F) for additional annunciation
functions.
Additional Application Data: Refer to Catalog No.
HKRNKA--1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordina tion. See Fig. 41.