100
MODE — CONFIGURATION (cont)
ITEM EXPANS I O N RANGE UNITS DEFAULT
CCN TABLE/
Sub--- TABLE
CCN POINT ENTRY
HMZR Humidimizer Config HMZR_C FG
REHT Humidimizer Equipped No/Yes N o : n o H u m i d i --- M i Z e r F I O P
Ye s : H u m i d i --- M i Z e r F I O P
REHEAT
R.DEC Reheat2 Stage Decr . Time 0 to 999 secs 60 RSTAGDEC
R.INC Reheat2 Stage Incr . Time 0 to 999 secs 300 RSTAGINC
RA.LO Reheat2 OAT Limit A 20 to 70 _F 40 OATLRH_ A
RA.LP Reheat2 SSP Lo Limit A 50 to 100 psig 80 RHSSPL_A
RA.HP Reheat2 SSP Hi Limit A 50 t o 100 psig 90 RHSSPH_A
RB.LO Reheat2 OAT Limit B 20 to 70 _F 50 OATLRH_B
RB.LP Reheat2 SSP Lo Limit B 50 to 100 psig 80 RHSSPL_B
RB.HP Reheat2 SSP Hi Limit B 50 to 100 psig 90 RHSSPH_B
HEAT Heating Con fi g u rati on HEAT_C F G
HT.TY Type of Heat Install ed 0=No Heat
1=Gas
2=Electric
0 (50 series with no electric heat)
1(48series)
2 (50 series with electric heat)
HEATTYPE
N.HTR N u m ber of Heat Stages 1to2 2
1(48seriesLowNox,50series
<15kW)
NUM_HEAT
MRT.H Heat M i n i mum On Time 60 to 999 sec 120 HMIN_ON
MOT.H Heat Minimum Off Time 60 to 999 sec 120 HMIN_OFF
H.DEC Heat Stage Decreas e Tim e 120 to 999 sec 300 HSTAGDEC
H.INC Heat Stage Inc re as e Tim e 120 to 999 sec 450 HSTAGINC
FOD.E Fan--- off Delay, El ect Heat 10 to 600 sec 30 ELEC_FOD
FOD.G Fan--- off Delay, Gas Heat 45 t o 600 sec 45 GAS_FOD
HT.LO Heating Lockout Temp 40 to 125 _F 75 OATLHEAT
SAT
SAT.H SA T Heat Mod e Sens i n g Disable/Enable Disable SAT_HEAT
SAM.L Maxim u m SAT Lower Level 85 to 200 _F 140 SATMAX_L
SAM.U Maximu m SAT Upper Level 85 to 200 _F 160 SATMAX_H
SPT Space Temperature
HT.PD SPT Heat Deman d (+ ) Leve l 0.5 to 5 ^F 1 HDEM_POS
HT.ND SPT Heat Deman d (--- ) Lev el --- 5 t o --- 0 . 5 ^F --- 1 HDEM_NEG
H.LAG Heat Therm al Lag F ac tor 0to5 1 HEAT_LAG
ECON Economizer Configuration ECON_CFG
EC.EN E con om iz er Ins tall ed No/Y es No: no FIOP
Yes: FIOP
ECONO
E.CTL Econ omi zer Con trol Type 1=Dig/Position
2=Dig/Command
3=Analog Ctrl
1 ECON_CTL
MP.25 Econ Min at 25% Fans peed 0 to 100 % 0 MINP_25
MP.50 Econ Min at 50% Fans peed 0 to 100 % 0 MINP_50
MP.75 Econ Min at 75% Fans peed 0 to 100 % 0 MINP_75
MP.MX Econ Min at Max Fans p eed 0 to 100 % 30
0: FIOP EnergyX
MINP_MAX
EC.MX Econo Cool Max P os iti on 0 to 100 % 100 ECONOMAX
M.ANG Min Ac tuator Ctrl Angle 75 to 90 88 MINANGLE
EH.LO Ec on o Cool Hi Temp Lim it 40 to 100 _F 65 OATLECLH
EL.LO Ec on o Cool Lo Temp Limit --- 30 to 50 _F 0 OATLECLL
DF.DB Diff Dry Bulb Control Dis able/Enable Disable DIFFBULB
UEFC Unoc cu p ied Free Coolin g 0=Disabled
1=Unoccpied
2=PreOccupancy
2 UEFC_CFG
FC.TM Free Cool PreOcc Tim e 1 t o 9999 mins 120 UEFCTIME
FC.LO Free Cool Low Temp Li mi t --- 30 to 70 _F 50 OATLUEFC
PE.EN P ower Exhaus t Installed No/Y es No: no FIOP
Yes: FIOP
PE_ENABL
PE.1 PE Stag e1 Econ o Pos i tion 0 to 100 % 40 PE1_POS
PE.2 PE Stag e2 Econ o Pos i tion 0 to 100 % 75 PE2_POS
PE1C Power Exhau s t Stage1 CFM 0 t o 15000 CFM 800 (04--- 07)
1600 (08--- 14)
3200 (17--- 28)
PE1_CFM
PE2C Power Exhau s t Stage2 CFM 0 t o 15000 CFM 0 PE2_CFM
IDF.C Indoor F an Max Speed CFM 500 to 15000 CFM 2000 (04--- 07)
4000 (08--- 14)
8000 (17--- 28)
IDF_CFM
EN.SW Enthalpy Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
ENTHLCFG
E.TRV Econ om iz er Travel Tim e 5 to 300 secs 150 ECONOTRV
E.MXB Bottom Stage Max Econo 0 to 100 % 50 ECONMAXB
E.MXT To p S t a g e M a x E c o n o 0 to 100 % 25 (03--- 14)
0 (17--- 28)
ECONMAXT
ComfortLINK v1.X