MODE CONFIGURATION (cont)
ITEM EXPANSIO N RANGE UNITS DEFAULT
CCN TABLE/
Sub--- TABLE
CCN POINT ENTRY
OAU (cont) Outside Air Unit Config OAU_CFG
TM.SP OA Tempring SA T Setpoint 35 to 80 _F 55 OA TMPSPT
OAC.K Outside Air CFM k Factor 0.8 to 1.2 1 OACFM_K
EXC.K Exhaust Air CFM k Factor 0.8 to 1.2 1 EXCFM_K
OAFB OAU F an Boos t Enab le No/Y es No EFB_ENBL
ALM.O Alarm Relay Conf ig . ALM_CFG
A.SPC SPT/SPRH Sensor Failure No/Yes Yes SPACE_AL
A.SRT SA T/RAT Sensor Failure No/Yes Yes SATRATAL
A.OAT OAT Th ermistor Failure No/Yes Yes OAT_AL
A.CMP Compressor Failu re No/Y es Yes COMP_AL
A.CKT Refrig Circuit Failu re No/Yes Yes CKT_AL
A.SSP SSP Transducer Failure No/Yes Yes SSP_AL
A.SCT SCT Thermistor F ailure No/Y es Yes SCT_AL
A.FAN Ind oor Fan F ai l u re No/Yes Yes FAN_AL
A.FIL Dirty Filter No/Y es Yes FILT_AL
A.TST Thermostat Failure No/Yes Yes TST AT_AL
A.ECO Econ om iz er Fai lu re No/Y es Yes ECON_AL
A.OAU Outside Air unit Alarms No/Yes Yes OAU_AL
PID PID Conf ig u r ation s PID_CFG
EC.P Econom izer PID --- kP 0.00 to 99.90 2.5 ECONO_P
EC.I Econom iz er PID --- kI 0.00 to 99.90 0.12 ECONO_I
EC.D Econ om izer PID --- kD 0.00 to 99.90 1 ECONO_D
EC.DT E con om i zer PID --- rate 10.00 to 180.00 secs 15 ECONO_DT
EC.DB Econ om iz er PID Deadban d 0to25 % 3 ECONBAND
LK.P Linkage Staging PID --- kP 0.00 to 99.90 10 LINK_P
LK.I Linkage Staging PID - -- kI 0.00 to 99.90 5 LINK_I
LK.D Linkage Staging PID --- kD 0.00 to 99.90 5 LINK_D
LK.DT Linkage Staging PID --- rate 10.00 to 180.00 secs 30 LINK_DT
(GENERIC =
CCN only)
GEN E R ICS
POINT 01 Definition Point_01
POINT 02 Definition Point_02
POINT 03 Definition Point_03
POINT 04 Definition Point_04
POINT 05 Definition Point_05
POINT 06 Definition Point_06
POINT 07 Definition Point_07
POINT 08 Definition Point_08
POINT 09 Definition Point_09
POINT 10 Definition Point_10
POINT 11 Definition Point_11
POINT 12 Definition Point_12
POINT 13 Definition Point_13
POINT 14 Definition Point_14
POINT 15 Definition Point_15
POINT 16 Definition Point_16
POINT 17 Definition Point_17
POINT 18 Definition Point_18
POINT 19 Definition Point_19
POINT 20 Definition Point_20
TRIM Sensor Calibration (CCN TRIM --- see
Maintenance Display)
SPT.C Space Temp Calib rati on --- 30 to 130 _F
SPT.T Space T emp T rim --- 30 to 30 ^F 0
SAT.C Supply Air Temp Calib. --- 30 to 130 _F
SAT.T Supply Air Temp Trim --- 30 to 30 ^F 0
RAT.C Return Air Temp Calib. --- 30 to 130 _F
RAT.T Return Air Temp Trim --- 30 to 30 ^F 0
CCN CCN Configuration CCN CONFIGURATION
CCN.A CCN E lem en t Numb er 1 to 239 1 48_50_HC CCNADD
CCN.B CCN Bus Number 0 to 239 0 CCNBUS
BAUD CCN Baud Rate 1=2400
2=4800
3=9600
4=19200
5=38400
3 CCNBAUDD
BROD CCN Broad c as t Conf ig . BRODEFS
B.TIM CCN Time/Date Broadcast No/Y es No CCNBC
B.OAT CCN OAT Broadcast No/Yes No OATBC
B.GS Global Sc h ed u l e Broadc s t No/Yes No GSBC
B.ACK CCN Broadcast Ack’er No/Yes No CCNBCACK