EasyManua.ls Logo

Carrier 48HD008 - START-UP - COOLING MODE; Cooling Start-Up Procedure; START-UP - HEATING MODE; Heating Start-Up Procedure

Carrier 48HD008
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
any
safety
trip,
and
indicator
light
on
thermostat
comes
on.
Check
reason
for
safety
trip.
Compressor
restart
is
accomplished
by
manual
reset
at
the
thermostat
by
turning
the
selector
switch
to
OFF
and
then
to
ON.
Heating
1.
Purge
gas
supply
line
of
air
by
opening
union
ahead
of
gas
valve.
When
gas
odor
is
detected,
tighten
union
and
wait
5
minutes
before
proceeding.
2.
Turn
on
manual
gas
valve
and
unit
electrical
supply.
3.
Set
system
switch
selector
at
HEAT
and
fan
switch
at
AUTO,
or
ON.
Set
heating
temperature
lever
at
above
room
temperature.
4.
The
induced
draft
combustion
air
fan
will
start.
Pilot
lights
within
30
seconds.
Refer
to
Service,
Pilot
Light
if
pilots
do
not
light.
5.
Main
gas
valve
will
open
and
main
burners
ignite
within
2
minutes
from
the
pilot
light
ignition.
Natural
gas
burners
are
factory
adjusted
and
should
burn
with
a
soft
blue
flame.
Flame
should
not
lift
off
burner
face.
Refer
to
Service,
Main
Burners,
if
required.
6.
Adjust
airflow
to
obtain
a
temperature
rise
with¬
in
the
range
specified
on
the
unit
nameplate.
TO
SHUT
OFF
UNIT
Set
system
selector
switch
at
OFF
or
set
heating
selector
lever
below
room
temperature.
Safety
Relief
A
soft
solder
joint
at
the
service
Schrader
port
provides
pressure
relief
under
abnormal
temperature
and
pressure
conditions.
Ventilation
{Continuous
Fan)
Set
fan
and
sys¬
tem
selector
switches
at
ON
and
OFF,
respectively.
Indoor
air
fan
operates
continuously
to
provide
constant
air
circulation.
Economizer
Operating
Sequence
COOLING
MODE
When
there
is
no
power
applied
to
the
indoor
fan
motor,
the
outdoor
damper
is
closed.
If
outdoor
ambient
temperature
is
above
the
outdoor
air
thermostat
(OAT.)
setting,
the
OAT.
contact
is
open.
No
power
is
supplied
to
DR2.
Upon
a
first-stage
call
for
cooling,
the
indoor
and
outdoor
fans
and
compressor
energize.
The
economizer
goes
to
vent
position.
If
outdoor
ambient
temperature
is
below
the
outdoor
air
thermostat
(OAT.)
setting,
the
OAT.
contact
is
closed
and
power
is
supplied
to
DR2
(normally
open
contacts
close
and
normally
closed
contacts
open).
Upon
a
first-stage
call
for
cooling
through
Y1,
power
goes
through
contacts
4
and
6
of
DR2
causing
DR1
to
energize
(normally
open
con¬
tacts
close
and
normally
closed
contacts
open).
The
economizer
switches
from
vent
or
closed
position
to
modulation
mode.
Modulation
is
accomplished
by
using
the
mixed
air
thermostat
(MAT.)
in
conjunction
with
the
stall
circuitry
inside
the
actuator.
If
the
mixed
air
temperature
is
above
the
MAT.
setting,
C-Tl
and
C-T2
are
made
causing
the
damper
motor
to
open
(which
causes
the
air
temperature
to
fall).
As
the
mixed
air
temperature
falls
to
the
MAT.
setting
(54
F),
C-T2
opens
causing
the
motor
to
stall.
When
mixed
air
temperature
goes
4F
below
the
MAT.
setting,
C-Tl
opens
causing
the
spring
to
close
the
damper.
This
in
turn
raises
the
mixed
air
tempera¬
ture
and
causes
C-Tl
to
again
stall
the
motor
into
a
less
than
full
open
position.
If
over-shoot
should
occur,
this
process
would
oscillate
a
few
times
until
the
mixed
air
temperature
stabilizes.
Upon
a
second-stage
call
for
cooling
through
Y2,
power
goes
through
contacts
1,3
and
5
of
DR2
and
CLO
and
the
compressor
is
energized.
Mechanical
cooling
is
integrated
with
economizer
cooling.
Economizer
continues
in
modulation
mode.
When
outdoor
ambient
temperature
goes
below
50
F,
the
cooling
lockout
switch
(CLS)
opens
and
mechanical
cooling
is
locked
out.
An
economizer
control
thermostat
(ECT)
on
the
evaporator
coil
guards
against
abnormally
low
suction
temperatures
while
operating
mechanical
cooling
in
conjunction
with
economizer.
Low
suction
temperatures
can
lead
to
frost
on
the
evap¬
orator
coil.
If
frost
buildup
is
detected,
thermostat
de-energizes
economizer,
thus
closing
the
outdoor
air
damper.
This
raises
air
temperature
entering
the
evaporator
coil
and
melts
frost.
Once
frost
is
melted,
the
economizer
is
re-energized.
When
cooling
load
is
satisfied,
the
damper
motor
is
de-energized
causing
the
spring
to
close
the
damper.
During
unoccupied
periods,
if
a
field-supplied
night
switch
is
used
and
is
opened,
the
outdoor
air
damper
closes.
HEATING
MODE
With
no
powerapplied
to
the
indoor
fan
motor,
the
outdoor
air
damper
is
closed.
Upon
a
call
for
heat
through
Wl,
the
indoor
fan
contactor
is
energized
and
provides
power
to
the
indoor
fan
motor
and
economizer.
If
the
night
set-back
switch
is
closed,
the
outdoor
dampers
will
open
to
the
manually
preset
vent
position
by
power
passing
through
contacts
1
and
2
of
DR
1
and
goingto
switches
SW1
and
SW2through
terminal
XV
of
actuator.
The
switches
are
set
with
3
degree
angular
difference
between
each
other,
acting
as
a
dead
spot
or
stall
region.
Thus,
if
the
damper
is
below
vent
position,
SW2
is
closed
power¬
ing
the
damper
open
until
SW1
closes
and
SW2
opens
which
stalls
the
motor.
If
the
damper
is
too
far
open,
both
SW1
and
SW2
are
open
causing
the
spring
to
close
the
damper
until
SW1
closes,
again
stalling
the
motor.
When
heating
load
is
satisfied,
the
damper
motor
is
de-energized
causing
the
spring
to
close
the
damper.
During
unoccupied
periods,
if
a
night
set-back
switch
is
used
and
opened,
the
damper
closes.
17

Related product manuals