EasyManua.ls Logo

Carrier 48HD008 - SERVICE - REFRIGERANT CHARGE; Cooling Charging Charts

Carrier 48HD008
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig.
35
Condenser
Air
Fan
Adjustment
Lubrication
COMPRESSORS
Each
compressor
is
charged
with
correct
amount
of
oil
at
the
factory.
FAN
MOTOR
BEARINGS
No
lubrication
of
condenser
or
evaporator
fan
motors
is
required
for
first
5
years
of
operation.
Annually
thereafter,
clean
and
repack
bearings
with
a
suitable
bearing
grease.
Condenser
Air
Fan
Adjustment
(Fig.
35)
Shut
off
unit
power
supply.
Remove
condenser
fan
assembly
(grille,
motor,
motor
cover
and
fan)
and
loosen
fan
hub
setscrews.
Adjust
fan
height
as
shown
in
Fig.
35.
Tighten
setscrews
and
replace
condenser
fan
assembly.
Manual
Outdoor
Air
Damper
(Downshot
Units
Only)
If
outdoor
air
damper
blade
adjustment
is
required,
see
Optional
Manual
Outdoor
Air
Damper
Section.
Economizer
Adjustment
(Downshot
Units)
Refer
to
Economizer
section
under
Installation.
Refrigerant
Charge
Amount
of
refrigerant
charge
is
listed
on
unit
nameplate
(also
refer
to
Table
1).
Refer
to
Carrier
Standard
Service
Tech¬
niques
Manual,
Chapter
1,
Refrigerants.
Unit
panels
must
be
in
place
when
unit
is
oper¬
ating
during
charging
procedure.
NO
CHARGE
Use
standard
evacuating
tech¬
niques.
After
evacuating
system,
weigh
in
the
speci¬
fied
amount
of
refrigerant.
(Refer
to
Table
1.)
LOW
CHARGE
COOLING
Using
Cooling
Charging
Chart,
Fig.
36
through
41,
vary
refrigerant
until
the
conditions
of
the
chart
are
met.
Note
the
charging
chart
is
different
from
type
normally
used.
Chart
is
based
on
charging
the
units
to
the
correct
superheat
for
the
various
operating
conditions.
Accurate
pressure
gage
and
temperature
sensing
device
are
required.
Connect
the
pressure
gage
to
the
service
port
on
the
suction
line.
Mount
the
tempera¬
ture
sensing
device
on
the
suction
line
and
insulate
it
so
that
outdoor
ambient
temperature
does
not
affect
the
reading.
Indoor
air
cfm
must
be
within
the
normal
operating
range
of
the
unit
(maximum
3750;
minimum
2250).
TO
USE
COOLING
CHARGING
CHART
Take
the
outdoor
ambient
temperature
and
read
the
suction
pressure
gage.
Refer
to
chart
to
determine
what
suction
temperature
should
be.
If
suction
tem¬
perature
is
high,
add
refrigerant.
If
suction
tempera¬
ture
is
low,
carefully
blow
some
of
the
charge.
Re¬
check
the
suction
pressure
as
charge
is
adjusted.
Example:
(Fig.
40)
Outdoor
Temperature.85
F
Suction
Pressure.
70
psig
Suction
Temperature
should
be.52
F
(Suction
Temperature
may
vary
±
5
F.)
co
<
o
2
620
Q_
O
_J
5
551
iii
or
§483
UJ
cc
CL
LlI
.
i
.
2
414
_i
z
o
P
345
o
3
CO
276
207
-
~
1
1
z
_J
105
41
CO
CL
SB
95
35
m
51
_
3
3
CO
CO
Ui
--
85
29
3
3
Em
CL
Ld
Z
_
K.W:I
w
2
o
1—
o
1
c
n
50
a
a
<
!
a
:
_
_
_
20
30
40
50
60
70
SUCTION
LINE
TEMPERATURE
(F)
-7
-i
4
10
16
21
SUCTION
LINE
TEMPERATURE
(C)
Fig.
36
Cooling
Charging
Chart;
48LDT004
Fig.
37
Cooling
Charging
Chart;
48HDT,LDT005
19

Related product manuals