Main
and
Pilot
Burners
At
the
beginning
of
each
heating
season,
inspect
for
deterioration
or
blockage
due
to
corrosion
or
other
causes.
Observe
the
pilot
and
main
burner
flames
and
adjust,
if
necessary,
referring
to
automatic
Pilot
Adjustment
or
Main
Burners
sections
of
instructions.
Flue
Gas
Passageways
Inspect
flue
collector
box
and
upper
areas
of
heat
exchanger
cells
by
removing
burner
compartment
access
panel;
then
remove
flue
cover
and
inspect
heat
exchangers.
Using
a
wire
brush,
clean
all
surfaces
as
required.
Combustion
Air
Blower
Clean
periodically
to
assure
proper
airflow
and
heating
efficiency.
Inspect
blower
wheel
every
fall
and
periodically
during
heating
season.
For
the
first
heating
season,
inspect
blower
wheel
bimonthly
to
determine
proper
clean¬
ing
frequency.
To
inspect
blower
wheel,
remove
draft
hood
and
screen.
Shine
a
flashlight
into
opening
to
inspect
wheel.
If
cleaning
is
required,
remove
motor
and
wheel
as
follows:
1.
Remove
burner
access
panel.
2.
Remove
the
6
screws
that
attach
induced
draft
motor
mounting
plate
to
blower
housing
(Fig.
42).
The
mounting
plate
will
drop
down.
3.
Remove
the
4
wires
attached
to
the
motor
and
remove
assembly
from
unit.
4.
To
remove
blower,
remove
setscrews.
5.
To
remove
motor,
remove
blower,
then
remove
the
nuts
that
hold
motor
to
mounting
plate.
NOTE:
Do
not
lose
spacers
for
induced
draft
motor.
6.
To
reinstall,
reverse
the
procedure
outlined
above.
Fig.
42
Burner
Section
Details
Limit
Switch
Access
panel
is
located
on
the
heat
section
side
panel
(Fig.
3
and
4).
004,005,006,007
UNITS
AND
48HDD,LDD/HD,
LD008
UNITS
Limit
switch
is
located
in
the
upper
section
of
the
heat
exchangers.
Bi-metal
sensor
is
facing
the
airstream.
Remove
bracket
holding
limit
switch
and
remove
screw
holding
switch.
48HHD,LHD/HH,LH008
UNITS
-
Limit
switch
is
located
on
partition
between
blower
section
and
heat
section.
Remove
plate
and
screw
holding
switch.
Pilot
Light
If
pilot
does
not
light
as
described
in
Start-Up,
Heating:
Be
sure
pilot
orifice
is
not
obstructed,
gas
pressure
is
not
less
than
3
in.
wg;
and
air
has
been
bled
from
gas
supply.
Check
for
spark
ignitor
malfunctions
as
follows:
1.
Shut
off
unit
power
supply.
2.
Check
that
spark
gap
is
1/8
to
3/16
inch.
3.
Check
that
spark
generator
is
securely
grounded
to
furnace
vestibule
plate.
4.
Check
that
high-voltage
lead
is
securely
con¬
nected
between
generator
and
electrode
body.
5.
Restore
power.
Check
that
24
volts
is
supplied
to
primary
side
of
generator.
6.
Check
unit
label
diagram
for
correct
terminal
usage
if
any
wires
are
removed.
Automatic
Pilot
Adjustment
1.
Turn
off
unit
power
supply,
set
system
selector
switch
at
HEAT,
and
adjust
thermostat
to
call
for
heat.
2.
Remove
burner
compartment
access
panel.
3.
Remove
screw
cap
cover
on
the
top
of
the
main
gas
valve
to
expose
pilot
adjusting
screw.
4.
With
a
small
screwdriver,
turn
adjustment
screw
until
flame
is
approximately
1
to
1-1/2
in.
high.
5.
Replace
screw
cap
cover
on
pilot
gas
valve.
6.
Observe
burner
operation
and
adjust
main
gas
valve
for
correct
burner
operation
as
required.
See
Fig.
43
for
proper
flame
appearance.
7.
Replace
all
panels.
Automatic
Gas
Valve
Sequence
of
Operation
Thermostat
calls
for
heat,
energizing
the
spark
ignitor
and
simultaneously
opening
the
pickup
and
hold
solenoids
of
the
pilot
gas
valve
(inside
main
gas
valve).
The
pilot
gas
ignites
within
2
seconds,
stop¬
ping
the
ignitor.
Within
11
seconds,
the
pilot
contact
(normally
closed)
opens,
drops
out
the
pickup
sole¬
noid.
Within
35
seconds,
the
pilot
contact
(normally
Fig.
43
Proper
Flame
Appearance
21