Table 1—Physical Data 48HJ
BASE UNIT 48HJ HJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006 HJD/E/F007
NOMINAL CAPACITY
3 4 5 6
OPERATING WEIG HT (lb)
Unit
530 540 560 635
Humidi-MiZer Adaptive Dehumidification System
15 23 25 29
EconoMi$er IV
50 50 50 50
Roof Cu r b
115 115 115 115
COMPRESSOR
Scroll
Quantity
1 1 1 1
Oil (oz)
42 53 50 60
REFRIGERANT TYPE
R-22
Expansion Device
Acutrol Metering Device
Operating Charge (lb-oz)
Standard U nit
5-8 10-2 10-0 12- 8
Unit With Humidi-Mizer Adaptive Dehumidification System
12-5 18-8 20-5 23-14
CONDENSER FAN
Propeller
Quantity...Diameter (in.)
1...22 1...22 1...22 1...22
Nominal Cfm
3500 3500 4100 4100
Motor Hp...Rpm
1
/
4
...825
1
/
4
...825
1
/
4
...1100
1
/
4
...1100
Watts Input (Total)
180 180 320 320
CONDENSER COIL
Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.
1...17 2...17 2...17 2...17
Total Face Area (sq ft)
14.6 16.5 16.5 21.3
EVAPORATOR COIL
Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Standard U nit
Rows...Fins/in.
2...15 2...15 4...15 4...15
Total Face Area (sq ft)
5.5 5.5 5.5 7.3
Unit with Humidi-Mizer Adaptive Dehumidification System
Rows...Fins/in.
1...17 2...17 2...17 2...17
Total Face Area (sq ft)
3.9 3.9 3.9 5.2
EVAPORATOR FAN
Centrifugal Type, Belt Drive
Quantity...Size (in.)
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10
Nominal Cfm
1200 1600 2000 2400
Maximum Continuous Bhp Std
1.20
1.20 1.30/2.40* 2.40
Hi-Static
2.40
2.40 2.90 2.90
Motor RPM Std
1620
1620 1725 1725
Hi-Static
1725
1725 1725 1725
Motor Frame Size Std
48
48 48/ 56* 56
Hi-Static
56
56 56 56
Fan Rpm Range Std
680-1044
770-1185 1035-1460 1119-1585
Hi-Static
1075-1455
1075-1455 1300-1685 1300-1685
Motor Bearing Type
Ball Ball Ball Ball
Maximum Fan Rpm
2100 2100 2100 2100
Motor Pulley Pitch Diameter A/B (in.)
Std
1.9/2.9
1.9/2.0 2.4/3.4 2.4/3.4
Hi-Static
2.8/3.8
2.8/3.8 3.4/4.4 3.4/3.4
Nominal Motor Shaft Diameter (in.) Std
1/
2
1
/
2
5
/
8
5
/
8
Hi-Static
5
/
8
5
/
8
5
/
8
7
/
8
Fan Pulley Pitch D iameter (in.) Std
4.5
4.0 4.0 4.0
Hi-Static
4.5
4.0 4.5 4.5
Belt Type...Length (in.) Std
1...A...36
1...A...36 1....4...40 1...A...38
Hi-Static
1...A...39
1...A...39 1...A...40 1...A...40
Pulley Center Line Distance (in.)
10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Std
65
70 75 95
Hi-Static
65
65 60 60
Movable Pulley Maximum Full
Turns from Closed Position
Std
5
5 6 5
Hi-Static
6
6 5 5
Factory Setting Full Turns Open Std
3
3 3 3
Hi-Static
3
1
/
2
3
1
/
2
3
1
/
2
3
1
/
2
Factory Speed Setting (rpm) Std
826
936 1248 1305
Hi-Static
1233
1233 1396 1396
Fan Shaft D iameter at Pulley (in.)
5
/
8
5
/
8
5
/
8
5
/
8
LEGEND
Bhp Brake Horsepower
*Single phase/three phase.
†Indicates automatic reset.
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000
Btuh heat input units have 3 burners. 115,000 Btuh heat input units a nd 150,000
Btuh Heat input units have 3 burners.
††An LP kit i s available as an accessory. Kit may be used at elevations as high as 2000
ft. If an LP kit is used with Low NOx units, the Low NOx baffle must be removed and
the units will no longer be classified as Low NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase stan-
dard models have one-stage heating with heating input values as follows:
HJD005-006,HJE004 72,000 Btuh
HJE005-006,HJF004 115,000 Btuh
HJF005-006 150,000 Btuh
***California compliant three-phase models.
†††California SCAQMD compliant low NO
x
models have combustion products that are
controlled to 40 nanograms per joule or less.