Table 11 — “Pressures” Mode and Submode Directory
Table 12 — “Set Points” Mode and Submode Directory
Table 13 — Reading and Changing Cooling Occupied Set Point
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
SSP.A XXX.X Saturated Suct Press A
SCP.A XXX.X Saturated Cond Press A Pressure is calculated
SSP.B XXX.X Saturated Suct Press B
SCP.B XXX.X Saturated Cond Press B Pressure is calculated
SSP.C XXX.X Saturated Suct Press C
SCP.C XXX.X Saturated Cond Press C Pressure is calculated
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
COOL
Cooling Set points
OCSP XX Occupied Cool Set point Default: 78
UCSP XX Unoccupied Cool Set point Default: 85
HEAT
Heating Set points
OHSP XX Occupied Heat Set point Default: 68
UHSP XX Unoccupied Heat Set point Default: 60
SAT
Supply Air Set points
LCSP XX Low Cool SAT Set point Default: 65
HCSP XX High Cool SAT Set point Default: 55
MIN.L XX.X Minimum SAT Lower Level Default: 48.0
MIN.H XX.X Minimum SAT Upper Level Default: 58.0
HC.SG
HC.SG XX Heat-Cool Set Point Gap Default: 5
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
COOL
OCSP 78 Occupied Cool Set point Default: 78
78 Scrolling Stops
78 Value flashes
Select 75
75 Change accepted
OCSP 75 Occupied Cool Set point Item/Value/Units scroll again
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE