Table 11 Pressures Mode and Submode Directory
Table 12 Set Points Mode and Submode Directory
Table 13 Reading and Changing Cooling Occupied Set Point
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
SSP.A XXX.X Saturated Suct Press A
SCP.A XXX.X Saturated Cond Press A Pressure is calculated
SSP.B XXX.X Saturated Suct Press B
SCP.B XXX.X Saturated Cond Press B Pressure is calculated
SSP.C XXX.X Saturated Suct Press C
SCP.C XXX.X Saturated Cond Press C Pressure is calculated
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
COOL
Cooling Set points
OCSP XX Occupied Cool Set point Default: 78
UCSP XX Unoccupied Cool Set point Default: 85
HEAT
Heating Set points
OHSP XX Occupied Heat Set point Default: 68
UHSP XX Unoccupied Heat Set point Default: 60
SAT
Supply Air Set points
LCSP XX Low Cool SAT Set point Default: 65
HCSP XX High Cool SAT Set point Default: 55
MIN.L XX.X Minimum SAT Lower Level Default: 48.0
MIN.H XX.X Minimum SAT Upper Level Default: 58.0
HC.SG
HC.SG XX Heat-Cool Set Point Gap Default: 5
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
COOL
OCSP 78 Occupied Cool Set point Default: 78
78 Scrolling Stops
78 Value flashes
Select 75
75 Change accepted
OCSP 75 Occupied Cool Set point Item/Value/Units scroll again
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE