APPENDIX E: BACnet Points List (cont)
Point Name Typ e
BACnet
Object ID
Alias
(CCN Point Name)
BACnet Object Name
Reset Filter Timer BMBV BV:109 reset_filter_timer
Run Auto Cool test BMBV BV:160 autocool
Run Auto Indepdent Test BMBV BV:163 autoindp
Run Auto System Test BMBV BV:162 autosys
SA Tempering Enable BMBV BV:410 sup_air_temp_en
SAT Sensor Error BMBV BV:84 sat_err
SDP A Sensor Error BMBV BV:63 sdpa_err
Shutdown A1 First BMBV BV:449 sdwn_a1
Shutdown A2 First BMBV BV:450 sdwn_a2
Shutdown ALD First BMBV BV:451 sdwn_ald
Shutdown In VFD Hand Mode BMBV BV:8 handshut
SPTO Sensor Error BMBV BV:7002 stpt_err
SPT Sensor Error BMBV BV:7001 spt_err
SSPA Sensor Error BMBV BV:89 sspa_err
Start DD restore BMBV BV:130 ddrstre
System Demand Alarm BMBV BV:26 sysdmdal sys_dmd_alarm
Temperature Compensated Start is active BMBV BV:133 tcs_act
Test Alarm Input BMBV BV:70 s_alarm
Test CCH Relay 1 BMBV BV:73 s_cchr1
Test Power Exhaust 1 BMBV BV:82 s_pe
Test Power Exhaust 2 BMBV BV:83 s_pe_2
Thermostat G Input BMBV BV:1021 g g_input
Thermostat W1 Input BMBV BV:1017 w1 w1_input
Thermostat W2 Input BMBV BV:1018 w2 w2_input
Thermostat Y1 Input BMBV BV:1019 y1 y1_input
Thermostat Y2 Input BMBV BV:1020 y2 y2_input
Thermostat Y3 Input BMBV BV:28 y3 y3_input
Today Is A Holiday BMBV BV:98 holtoday
Tomorrow Is A Holiday BMBV BV:96 hol_tmrw
Unoccupied Free Cooling Active BMBV BV:135 ufc_act
USB Find Restore File BMBV BV:111 backfile
VFD 1 Reverse? BMBV BV:102 vfd1mdir
VFD Config OK? BMBV BV:105 vfdcfgok
VFD Reverse Select BMBV BV:69 rev_sel
Active Occupancy Control BMSV MSV:14 occ_ctrl
ALC Status color BMSV MSV:9 color
Alert from thermostat BMSV MSV:8 tstat_alert
BACnet BMS baud rate BMSV MSV:18 bac_baud
BMS Configuration BMSV MSV :11 bms_cfg
BMS Occupancy Request BMSV MSV:12 bms_occ
Communications status BMSV MSV:17 e0commst
Cool demand Limit Level BMSV MSV:56 cdlm_level
FBD Type BMSV MSV:58 fbd_type
Filter Status Switch Inp BMSV MSV:41 filter_channel
Filter Status Swith Type BMSV MSV:42 filt_cfg
Firmware Release State BMSV MSV :19 fw_state
Heat demand Limit Level BMSV MSV:57 hdlm_level
Heat Type BMSV MSV:16 heattype ht_type
IAQ Analog Input Config BMSV MSV :25 iaqancfg
IDF Type BMSV MSV:450 idftype
IDF VFD Fault Detail BMSV MSV:23 svfdflt
Keep Configuration BMSV MSV :47 keepconf
Linkage Occupancy request BMSV MSV:13 lnk_occ
Motor Power BMSV MSV:22 MOTPWR mot_pwr
Remote Occupancy Config BMSV MSV:45 rmoc_cfg
RFI Filter BMSV MSV :4 rfi_filter
Running Mode Operation BMSV MSV:43 sub_mode
Switching Frequency BMSV MSV:7 switch_freq
System Demand BMSV MSV:101 sys_dmde sys_demand_enum
System Mode BMSV MSV:2002 sysmode sys_mode
SystemVu Type BMSV MSV:2003 sysvtype
Test Inactivity Time Out BMSV MSV:156 test_ito
Thermostat Type BMSV MSV :5 stattype tstat_type
Unit Control Type BMSV MSV :2 control_type
Unocpied Free Cooling config BMSV MSV:24 ufc_cfg
Ventilation Status BMSV MSV:6 ventstat
VFD1 Warning Detail BMSV MSV:3001 vfd_warning