100
ALARM RELAY (cont)
HEATING ALERTS Heating Failure Alerts Yes/No Yes HEAT_AL
INDOOR FAN ALERTS Indoor Fan Alerts Yes/No Yes FAN_AL
VFD ALERTS VFD Alerts Yes/No Yes VFD_AL
IO BOARD ALERTS Relay On Active IOBA Yes/No No IOBFA_AL
ON ACTIVE FAULTS Relay on Active Faults Yes/No Yes FAULT_AL
SERVICE CONFIG MENU Service Configuration Menu
CMP FRAMEWORK Compressor Framework
0=1CIR 2CMP,
1=1CMP+LDR,
2=1CMP
0 (sizes 07-26)
1 (sizes 04-06)
SYSVTYPE
SHUTDWN A1 FIRST Comp A1 Shutdown First Yes/No
Yes (sizes 07-26)
No (sizes 04-06)
SDWN_A1
SHUTDWN ALD FIRST Comp Loader Shutdown 1st Yes/No
No (sizes 07-26)
Yes (sizes 04-06)
SDWN_ALD
SIOB1 INSTALLED SIOB 1 Enabled Yes/No
No: no Humidi-Mizer
FIOP
Yes: Humidi-Mizer
FIOP
SIOB1_EN
ECONO PID - KP ECONO PID - KP 0.00 to 99.90 2.5 ECONO_P
ECONO PID - KI ECONO PID - KI 0.00 to 99.90 0.12 ECONO_I
ECONO PID - KD ECONO PID - KD 0.00 to 99.90 1 ECONO_D
ECONO PID - RATE ECONO PID - RATE 10 to 180 sec 15 ECONO_DT
FBD PID Kp FBD PID Kp 0 to 99.99999 0.01 FBDPID_P
FBD PID Ki FBD PID Ki 0 to 99.99999 0 FBDPID_I
FBD PID Kd FBD PID Kd 0 to 99.99999 0 FBDPID_D
FBD KI RESET VAL FBD Ki Reset Val. 0 to 99.9 0 FBDKIRES
ODF ADVANCED CONFIGS
Outdoor Fan Advanced Configs
Menu
ODF GAIN ODF Gain –100 to 100
1 (sizes 07)
2 (sizes 08-12)
1.8 (sizes 14-20)
1.4 (sizes 04-06,
24-26)
ODF_KC
ODF ANTI-WINDUP ODF anti-windup factor –100 to 100 0.6 ODF_NI
ODF INTEGRAL TIME ODF Integral Time –100 to 100
20 (sizes 04-12)
40 (sizes14-26)
ODF_TI
ODF MBIAS 1 ODF Map Bias Term 1 –200 to 200
66.7 (sizes 07)
-44.55 (sizes 08-12)
10 (sizes 14-20)
72.5 (sizes 04-06,
24-26)
ODFBIAS1
ODF MBIAS 2 ODF Map Bias Term 2 –200 to 200
95.2 (sizes 07)
80.59 (sizes 08-12)
35.3 (sizes 14-20)
100.98 (sizes 04-06,
24-26)
ODFBIAS2
ODF MBIAS 3 ODF Map Bias Term 3 –200 to 200
0 (sizes 07, 14-20)
20.93 (sizes 04-06)
65.29 (sizes 08-12)
114.74 (sizes 24-26)
ODFBIAS3
ODF SWITCH POINT1 ODF Fans Switch Point 1 –100 to 100
3.68 (sizes 07)
3.4 (sizes 08-12)
4.84 (sizes 14-20)
1.58 (sizes 04-06,
24-26)
ODFPIUP1
ODF SWITCH POINT2 ODF Fans Switch Point 2 –100 to 100
17.1 (sizes 07)
9.06 (sizes 08-12)
22.3 (sizes 14-20)
10.44 (sizes 04-06,
24-26)
ODFPIUP2
ODF SWITCH POINT3 ODF Fans Switch Point 3 –100 to 100
100 (sizes 07, 14-20)
19.76 (sizes 08-12)
20.93 (sizes 04-06,
24-26)
ODFPIUP3
ODF PROP PR ODF Proportional ctrl Pr –100 to 100
25 (sizes 07-12)
50 (sizes 04-06,
14-26)
ODFPR_KC
ODF MSLOPE 1 ODF Map Slope Term 1 –100 to 100
25.3 (sizes 07)
60.09 (sizes 08-12)
31 (sizes 14-20)
55.33 (sizes 04-06,
24-26)
ODFSLPE1
Table B — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY