101
SERVICE CONFIG MENU (cont)
ODF MSLOPE 2 ODF Map Slope Term 2 –100 to 100
9 (sizes 07)
18.69 (sizes 08-12)
9.6 (sizes 14-20)
19.07 (sizes 04-06,
24-26)
ODFSLPE2
ODF MSLOPE 3 ODF Map Slope Term 3 –100 to 100
1 (sizes 07, 14-20)
9.34 (sizes 08-12)
8.85 (sizes 04-06, 24-
26)
ODFSLPE3
NEW HARDWARE Quick Menu for New Hardware
UNIT CONTROL TYPE Unit Control Type
0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
ECON INSTALLED? Economizer Installed? Yes/No
No: no FIOP
Yes: FIOP
ECONO
SPRH SENS CHANNEL SPRH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB Ai10
0=None SPRHCHAN
IAQ SENSOR CHAN IAQ Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
1: no FIOP
0: FIOP
IAQ_CHAN
OAQ SENSOR CHAN OAQ Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None OAQ_CHAN
OARH SENSOR CHAN OARH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
3: no FIOP
0: FIOP
OARHCHAN
RARH SENS CHANNEL RARH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None RARHCHAN
OACFM SENS CHANNEL OACFM Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB Ai10
0=None OCFMCHAN
FIRE SHUTDOWN SW Fire Shutdown Switch
0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
FILTER SW CHANNEL Filter Status Sw Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None FILTCHAN
REMOTE OCC CHAN Remote Occupancy Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None RMOCCHAN
REM.SHUTDOWN CHAN Remote Shutdown Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ROFFCHAN
COFS CHANNEL COFS Assigned Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None COFSCHAN
GEN STATUS CHAN General Status Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None GEN_CHAN
Table B — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY