Table L — MODE – SETPOINTS
ITEM EXPANSION RANGE UNIT DEFAULT POINT
SETPOINTS
OCSP Occupied Cool Setpoint 55 to 80 °F 78 OCSP
OHSP Occupied Heat Setpoint 55 to 80 °F 68 OHSP
UCSP Unoccupied Cool Setpoint 65 to 95 °F 85 UCSP
UHSP Unoccupied Heat Setpoint 40 to 80 °F 60 UHSP
GAP Heat-Cool Setpoint Gap 2 to 10 ^F 5 HCSP_GAP
STO.R SPT Offset Range (±) 0 to 5 °F 5 SPTO_RNG
RH.SP Space RH Setpoint 0 to 100 % 55 SPRH_SP
SA.SP SA Tempering Setpoint xx °F 50 SATEMPSP