GENDISP
Circuit A Pressure Ratio xx.xx CIRA_PR
Barometric Pressure xx.xx in.Hg BARP Forcible
Filter hour remaining xxxx hours FILTLEFT
Reset Filter Timer Yes/No RESETFLT Writable
Outdoor Air Enthalpy xxx.x Btu/lb OA_ENTH Forcible
Return Air Enthalpy xxx.x Btu/lb RA_ENTH Forcible
Differential Air Quality xxxx ppm AQ_DIFF
DST currently active Yes/No DST_ACTV
Network OAT Value xxx.x °F OAT_NET Forcible
Network Return Air Temp xxx.x °F RAT_NET Forcible
Network Space Temp Value xxx.x °F SPT_NET Forcible
Network SPRH Value 0 to 100 % SPRH_NET Forcible
Network OARH Value 0 to 100 % OARH_NET Forcible
Network RARH Value 0 to 100 % RARH_NET Forcible
Network IAQ Value xxxx ppm IAQ_NET Forcible
Network OAQ Value xxxx ppm OAQ_NET Forcible
Network OACFM Value xxx.x cfm OCFM_NET Forcible
MODEDISP
System Mode see Appendix B SYSMODE
Running Mode Operation see Appendix B SUB_MODE
Ventilation Status see Appendix B VENTSTAT
System Demand 0 to 99 SYS_DMD
Currently Occupied Yes/No OCCUPIED Forcible
Linkage Active Yes/No LNK_ACT Forcible
Unocc Free Cool Active Yes/No UFC_ACT
Temp Compensate Start On Yes/No TCS_ACT
Cool Setpoint In Effect xx.x °F CSP_EFF
Heat Setpoint In Effect xx.x °F HSP_EFF
Effective Demand Temp xxx.x °F TEMP_EFF
Cool Demand Limiting Off 0 to 1 CDMLMOFF
Cool Demand Limit Offset 0 to 99 °F COOLDLMO
Heat Demand Limiting Off 0 to 1 HDMLMOFF
Heat Demand Limit Offset 0 to 99 °F HEATDLMO
Cool Demand Limit Level 0 to 3 CDMDLLEV
Heat Demand Limit Level 0 to 3 HDMDLLEV
IDF_DISP
Commanded IDF Speed 0 to 100 % FANSPEED
IDF VFD Actual Speed % 0 to 100 % MAV
IDF Speed Override Flag On/Off FAN_OVRD
IDF Operation Errors? Yes/No IDFBAD
IDF Speed Reduction On Yes/No FANRED10
IDF VFD Output Amps 0 to 655.35 Amps OUTMCUR
IDF VFD Output Power hp 0 to 1000 OUTPWRHP
IDF VFD Fault Detail
0=NONE,
1=PWR CARD,
2=EARTH FLT,
3=CTRL WORD,
4=OVER CURR,
5=OVER TEMP,
6=OVERLOAD,
7=UNDERVOLT,
8=OVER VOLT,
9=SHORT CIR,
10=PHASELOSS,
11=U LOSS,
12=V LOSS,
13=W LOSS,
14=CTRL VOLT,
15=VDD LOW,
16=MULTIPLE,
17=UNEXPECT
SVFDFLT
IDF VFD Warning Detail
0=NONE,
1=VOLTAGE,
2=CURRENT,
3=THERMAL,
4=MULTIPLE,
5=UNEXPECT
SVFDWAR
Table S — Status Display Tables (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES