157
BACNET (cont)
Object instance for SPT 0 to 9999 OBJSPT 2007
Change of value for SPT 0 to 60 COVSPT 0
Allow Local Sched Edit Yes/No LCL_EDIT
BRODEFS
CCN Broadcast Ack’er Yes/No CCNBCACK No
Global Schedule Broadcast Yes/No CCN_GSBC No
CCN Time Broadcast Yes/No CCNBC No
Broadcast OAT On Network Yes/No OATBC No
Broadcast OARH On Network Yes/No OARHBC No
Broadcast OAQ On Network Yes/No OAQBC No
Broadcast IAQ On Network Yes/No IAQBC No
DST allowed? Enable/Disable DST_CFG Enable
DST Start Month
1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEMBER,
12=DECEMBER
STARTM 3=MARCH
DST Start Week 1 to 5 STARTW 2
DST Start Day
1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
STARTD 7=SUNDAY
DST Minutes to Add 0 to 90 min MINADD 60
DST Stop Month
1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEMBER,
12=DECEMBER
STOPM 11=NOVEMBER
DST Stop Week 1 to 5 STOPW 1
DST Stop Day
1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
STOPD 7=SUNDAY
DST Minutes to Subtract 0 to 90 min MINSUB 60
Time in day to start DST 0 to 600 min DST_TOD 120
ALARMDEF
Alarm Routing Control 00000000 to 11111111 ALRM_CNT 11000000
Equipment Priority 0 to 7 EQP_TYPE 5
Comm Failure Retry Time 1 to 240 min RETRY_TM 10
Re-Alarm Time 1 to 255 min RE-ALARM 180
Alarm System Name up to 8 alphanum ALRM_NAM 48_50LC_
HOLIDAY
HOLDYxxS
MON Holiday Start Month 1 to 12 = January to December HD01STMN - HD30STMN 0
DAY Holiday Start Day 1 to 31 HD01STDY - HD30STDY 0
LEN Holiday Duration (days) 1 to 99 HD01LEN - HD30LEN 0
(repeat up to xx=30
Holidays)
Table V — CONFIGURATION TABLES (cont)
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES