The SystemVu controller is i-Vu
®
compatible and includes
equipment and view files that organize the BACnet points for
the graphic page and property pages in i-Vu. The controller
supports single point linkage, proprietary i-Vu zoning linkage,
and the BACnet notification object for alarms.
When notification of alarms is turned off, this does not mean
the Alarm condition has been cleared. It just means the notifi-
cation of the alarm has been temporarily stopped. If the alarm
condition still exists after a delay, the notifications will start be-
ing sent again.
Table W — SETPOINT TABLE
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
SET_PNT
Occupied Cool Setpoint 55 to 80 °F OCSP 78
Occupied Heat Setpoint 55 to 80 °F OHSP 68
Unoccupied Cool Setpoint 65 to 95 °F UCSP 85
Unoccupied Heat Setpoint 40 to 80 °F UHSP 60
Heat-Cool Setpoint Gap 2 to 10 ^F HCSP_GAP 5
SPT Offset Range (±) 0 to 5 °F SPTO_RNG 5
Occupied SPRH Setpoint 0 to 100 % SPRH_OSP 55
Unoccupied SPRH Setpoint 0 to 100 % SPRH_USP 55
Table X — CONTROL ID TABLE
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
CTLRID
Device Name: 48_50LC_
Description: text string
Location: text string
Software Part Number: CESR131651-XX-XX
Model Number: xxxxxxxxxxxxxxxxxx
Serial Number: xxxxxxxxxx
Reference Number:
Table Y — BACnet* AV Points List
POINT DESCRIPTION POINT ACCESS UNITS
BACNET
OBJECT NAME
BACNET
ID
VALUE
RANGE
CCN POINT
EQUIVALENT
A1 Loader Resets Count READ ONLY rs_aldr AV:7012 0 to 65535 RS_ALDR
Actual Cool Stage Active READ ONLY actcstgs AV:194 0 to 3 ACTCSTGS
Actual fan status R/W idf_status AV:190 0 to 100 IDF_STAT
Actual Heat Stage Active READ ONLY acthstgs AV:46 0 to 2 ACTHSTGS
Alarm display info READ ONLY alarm_info AV:14 0 to 2 ALARM
Alarm Relay Resets Count READ ONLY rs_alm AV:99 0 to 65535 RS_ALM
Alarm Relay Run Hours READ ONLY hrs hour_alarm AV:49 0 to 999999 HR_ALM
Alarm Relay Starts READ ONLY st_alm AV:136 0 to 999999 ST_ALM
Alarm Reset Counts READ ONLY st_alrst AV:137 0 to 999999 ST_ALRST
Alarm Reset Resets Count READ ONLY rs_alrst AV:100 0 to 65535 RS_ALRST
AQ Diff Low-IAQ OVERRIDE R/W PPM aqd_low AV:443 0 to 5000 AQD_LOW
AQ Differential High R/W daq_high AV:212 0 to 5000 DAQ_HIGH
AQ Differential Low R/W daq_low AV:213 0 to 5000 DAQ_LOW
AQ DiffHigh-IAQ OVERRIDE R/W PPM aqd_high AV:442 0 to 5000 AQD_HIGH
Average Occup. Cool Stp. R/W °F lnk_ocsp AV:264 55 to 80 LNK_OCSP
Average Occup. Heat Stp. R/W °F lnk_ohsp AV:266 55 to 80 LNK_OHSP
Average Occup. Zone Temp R/W °F lnk_aozt AV:255 –40 to 245 LNK_AOZT
Average Unocc. Cool Stp. R/W °F lnk_ucsp AV:274 65 to 90 LNK_UCSP
Average Unocc. Heat Stp. R/W °F lnk_uhsp AV:275 40 to 80 LNK_UHSP
Average Zone Temperature R/W °F lnk_azt AV:256 –40 to 245 LNK_AZT
BACKUP Preparation Time READ ONLY bkpreptm AV:336 0 to 65535 BKPREPTM
BACnet device for IAQ R/W deviaq AV:8001 0 to 4194303 DEVIAQ
BACnet device for OAQ R/W devoaq AV:8002 0 to 4194303 DEVOAQ
BACnet device for OARH R/W devoarh AV:8004 0 to 4194303 DEVOARH
BACnet device for OAT R/W devoat AV:8003 0 to 4194303 DEVOAT
BACnet device for RARH R/W devrarh AV:8005 0 to 4194303 DEVRARH
BACnet device for RAT R/W devrat AV:8006 0 to 4194303 DEVRAT
BACnet device for SPRH R/W devsprh AV:8028 0 to 4194303 DEVSPRH
BACnet device for SPT R/W devspt AV:8007 0 to 4194303 DEVSPT
BACnet Device Macaddress R/W bac_mac AV:189 0 to 127 BAC_MAC
BACnet ID Number R/W bac_id AV:188 0 to 4194302 BAC_ID