Table Z — BACnet* BV Points List
POINT DESCRIPTION POINT ACCESS UNITS
BACNET
OBJECT NAME
BACNET
ID
VALUE
RANGE
CCN POINT
EQUIVALENT
IDF VFD Hand Fault R/W f_vfdhnd BV:233 0 to 1
IDF VFD Lockout FltActv R/W f_vfdlo BV:234 0 to 1
IDF VFD Loss of Comm R/W f_idfcom BV:229 0 to 1
A051 Cmp off expected ON R/W a_caoff BV:181 0 to 1
Act Mech Disconnect Alrt R/W a_dnmemd BV:218 0 to 1
Air Quality CO2 Alerts R/W co2s_al BV:307 0 to 1 CO2S_AL
Alarm Output Relay State R/W equip_alarm BV:7048 0 to 1 ALMOUT
Alarm Output Relay Test R/W s_alarm BV:70 0 to 1 S_ALARM
Alarm Reporting Enable R/W ALARMEN BV:27 0 to 1 ALARMEN
ALC Auto Id Scheme R/W auid BV:106 0 to 1 AUID
All Heat Stages Lockout R/W allhtloc BV:122 0 to 1 ALLHTLOC
AUTO INDEPENDENT TEST R/W autoindp BV:163 0 to 1 AUTOINDP
BACnet BMS Schedule READ ONLY bms_sced BV:108 0 to 1 BMS_SCED
BACnet ID Auto ID R/W bac_auid BV:107 0 to 1 BAC_AUID
BACnetCal Object Status READ ONLY calobjst BV:110 0 to 1 CALOBJST
Bad DD Point-OutOfRange R/W f_bad_dd BV:243 0 to 1
CA1 DDF Fault R/W f_ca1ddf BV:178 0 to 1
CA1 FTP alert R/W a_ca1ftp BV:182 0 to 1
CA1 Rev Rotation alert R/W a_ca1rr BV:179 0 to 1
CA2 DDF fault R/W f_ca2ddf BV:173 0 to 1
CA2 FTP alert R/W a_ca2ftp BV:177 0 to 1
CA2 Rev Rotation alert R/W a_ca2rr BV:174 0 to 1
CCH Relay 1 State READ ONLY cch_relay BV:3 0 to 1 CCHR1
Cir A DDF Fault R/W f_caddf BV:168 0 to 1
Cir A HDP alert R/W a_cahdp BV:172 0 to 1
Cir A HPS alert R/W a_cahps BV:171 0 to 1
Cir A LDP Alert R/W a_caldp BV:236 0 to 1
Cir A LSP Alert R/W a_calsp BV:170 0 to 1
Cir A Press Ratio Alert R/W a_capr BV:169 0 to 1
Cir A SSP out Rng Alert R/W a_badspa BV:189 0 to 1
Cir.A High Pressure Sw READ ONLY circa_hps BV:4 0 to 1 CIRA_HPS
Circ A SDP Open Alert R/W a_opndpa BV:191 0 to 1
Circ A SDP range alert R/W a_baddpa BV:183 0 to 1
Circ A SDP Short Alert R/W a_shtdpa BV:202 0 to 1
Circ A SSP Open Alert R/W a_opnspa BV:200 0 to 1
Circuit A CMP A1 Loader READ ONLY cmpalena BV:9 0 to 1 COMP_ALD
Circuit A Compressor 1 READ ONLY cmpa1ena BV:5 0 to 1 COMP_A1
Circuit A Compressor 2 READ ONLY cmpa2ena BV:6 0 to 1 COMP_A2
Circuit A Locked Out READ ONLY ciralock BV:128 0 to 1 CIRALOCK
Circuit A SSP Shrt Alert R/W a_shtspa BV:211 0 to 1
Ckt-A low charge fault R/W f_caloch BV:167 0 to 1
Clear Alarm History R/W alarm_hist_clear BV:32 0 to 1 ALHISCLR
Cmp Bump Loader Test R/W s_bmpald BV:64 0 to 1 S_BMPALD
COFS Switch State R/W condensate_switch BV:7028 0 to 1 COFS
Compressor A1 Available READ ONLY ca1_aval BV:123 0 to 1 CA1_AVAL
Compressor A1 Locked Out READ ONLY ca1_lock BV:124 0 to 1 CA1_LOCK
Compressor A2 Available READ ONLY ca2_aval BV:125 0 to 1 CA2_AVAL
Compressor A2 Locked Out READ ONLY ca2_lock BV:126 0 to 1 CA2_LOCK
Compressor Alerts R/W comp_alarm BV:312 0 to 1 COMP_AL
Compressor Bump A1 Test R/W s_bmpa1 BV:71 0 to 1 S_BMPA1
Compressor Bump A2 Test R/W s_bmpa2 BV:72 0 to 1 S_BMPA2
CompressorStuck on Fault R/W f_cstuck BV:241 0 to 1
Condensate Ovrflow fault R/W f_cofs BV:273 0 to 1
CoolDemandLimiting R/W cooldmdLimit BV:435 0 to 1 CDMLMOFF
Cooling Liq Valv Test R/W s_clv_a BV:456 0 to 1 S_CLV_A
Cooling Liq Valve CirA R/W clv_a BV:7052 0 to 1 CLV_A
Cooling W/Comp.A1 Test R/W s_coola1 BV:74 0 to 1 S_COOLA1
Cooling W/Comp.A2 Test R/W s_coola2 BV:75 0 to 1 S_COOLA2
Cooling W/Comp.ALD Test R/W s_cola1d BV:79 0 to 1 S_COLALD
Crankcase Heater 1 test R/W s_cchr1 BV:73 0 to 1 S_CCHR1