90
COOL (cont)
ECON OPERATIONAL? Econ Damper Operational Yes/No DAMPGOOD
DRY BULB LOCKOUT Dry Bulb Lockout Yes/No Forcible DBLOCK
ENTHALPY LOCKOUT Enthalpy Lockout Yes/No Forcible ENTHLOCK
OK TO UNOCC FC? Ok to Unocc Free Cool? Yes/No OKTOUFC
IN UNOC FREECOOL? Unocc Free Cool Active Yes/No UFC_ACT
UFC LOCKOUT? Unocc Free Cool Lockout Yes/No UNOCLOCK
DEHUM DEHUM
OK TO DEHUM Ok to Dehumidify? Yes/No/locked out OKTODHUM
OD TO FAN BASE DH Ok to fan based dehum? Yes/No OKTOFBD
HUMIDIMIZER OK Ok to use humidimizer? Yes/No OKTOHUMZ
REQ. DEHUM STGS Req Compr Dehum Stgs 0 to 3 REQDSTGS
FBD SST LOCKOUT FBDH SST Lockout Yes/No FBDSSTLO
FBD SAT LOCKOUT FBDH SAT Lockout Yes/No FBDSATLO
HEAT Heating Status Menu
IDF SPEED OUTPUT Commanded IDF Speed 0 to 100 % FANSPEED
IGC FAN REQUEST IGC Fan On Request (IFO) On/Off IGC_IFO
REG. HEAT STAGES Requested Heating Stages 0 to 2 REQHSTGS
ACTIVE HEAT STAGE Actual Heat Stage Active x ACTHSTGS
OK TO USE HEAT? OK to Run Heat? Yes/No OKTOHEAT
MAX HEAT STAGES Max Allowed Heat Stages 0 to 2 Forcible MAXHSTGS
HEAT 1 TIMEGUARD Heat Stage 1 Timeguard xxx sec TIMGD_H1
HEAT 2 TIMEGUARD Heat Stage 2 Timeguard xxx sec TIMGD_H2
SUPPLY AIR TREND Supply Air Temp Trend xxx.x ^F/min SATTREND
HEAT LOCKOUT All Heat Stages Lockout Yes/No Forcible ALLHTLOC
HEAT 1 AVAILABLE Heat Stage 1 Available Yes/No HT1_AVAL
HEAT 2 AVAILABLE Heat Stage 2 Available Yes/No HT2_AVAL
OK TO SA TEMPER OK to Supply Air Tempering Yes/No OKTOTEMP
VENTILATION Ventilation Status Menu
VENT MODE Ventilation Status see Appendix B VENTTEXT
EFFECTIVE MIN POS Min Position in Effect 0 to 100 % Forcible MIN_POS
ECON ACT POSITION Econo Actual Position 0 to 100 % DAMPPOS
IDF SPEED OUTPUT Commanded IDF Speed 0 to 100 % FANSPEED
OCCUPIED NOW Currently Occupied Yes/No Forcible OCCUPIED
IN PREOCC PURGE? In Pre-Occupancy Purge? Yes/No PREOCCON
IN FREE COOLING Free Cooling Active Yes/No FREECOOL
DIFF AIR QUALITY Differential Air Quality xxxx ppm AQ_DIFF
OK TO PREOC PURGE Ok to Preoccupancy Purge Yes/No OKPREOCC
Override IAQ? Is IAQ Override Active? Yes/No enum IAQ_OVRD
IAQ OVRRD SW STAT IAQ Override SW state Yes/No enum IAQ_OVRS
DCV CURVE OFFSET IAQ DCV Curve Offset 0 to 100 % IAQ_OFFS
INDOOR FAN Indoor Fan Status Menu
IDF SPEED OUTPUT Commanded IDF Speed 0 to 100 % FANSPEED
IDF VFD FEEDBACK IDF VFD Actual Speed % 0 to 100 % MAV
IDF SPD OVERRIDE IDF Speed Override Flag On/Off enum FAN_OVRD
IDF ERRORS? IDF Operation Errors? Yes/No enum IDFBAD
IDF SPD REDUCTION IDF Speed Reduction On Yes/No enum FANRED10
VFD OUTPUT AMPS IDF VFD Output Amps xxx.xx amps OUTMCUR
VFD OUTPUT HP IDF VFD Output Power HP xxxx.x HP OUTPWRHP
VFD FAULT DETAIL IDF VFD Fault Detail
0=NONE,
1=PWR CARD,
2=EARTH FLT,
3=CTRL WORD,
4=OVER CIRR,
5=OVERLOAD,
7=UNDERVOLT,
8=OVER VOLT
9=SHORT CIR,
10=PHASELOSS,
11=U LOSS,
12=V LOSS,
13=W LOSS,
14=CTRL VOLT,
15=VDD LOW,
16=MULTIPLE,
17=UNEXPECT
SVFDFL
Table A — Run Status Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT VALUES UNITS WRITE STATUS POINT
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY

Table of Contents

Other manuals for Carrier 48LC Series

Related product manuals