95
ANALOG INPUT CONFIGS
(cont)
OAQ SENSOR CHAN OAQ Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None OAQ_CHAN
OAQ PPM@ 4MA OAQ Sensor Value at 4mA 0 to 5000 ppm 0 OAQ_4MA
OAQ PPM@ 20MA OAQ Sensor Value at 20mA 0 to 5000 ppm 2000 OAQ_20MA
OARH SENSOR CHAN OARH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no Enthalpy FIOP
3: Enthalpy FIOP
OARHCHAN
OARH RH @ 4MA OARH Sensor Value at 4mA 0 to 100 % 0 OARH_4MA
OARH RH @ 20MA OARH Sensor Val. at 20mA 0 to 100 % 100 OARH20MA
RARH SENS CHANNEL RARH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None RARHCHAN
RARH RH @ 4MA RARH Sensor Value at 4mA 0 to 100 % 0 RARH_4MA
RARH RH @ 20MA RARH Sensor Value at 20mA 0 to 100 % 100 RARH20MA
OACFM SENSOR CHAN OACFM Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0=None OCFMCHAN
OACFM@ 4MA OACFM value at 4mA 0 to 100 CFM 0 OCFM_4MA
OACFM@ 20MA OACFM Value at 20mA 0 to 100 CFM 20 OCFM20MA
COOLING Cooling Configurations Menu
LOW COOL COMP Low Cool Compressor 1 to 2 1 LC_COMP
COMP MIN ON TIME Compressor Min On Time 180 to 600 sec 300 C_MINON
COMP MIN OFF TIME Compressor Min Off Time 120 to 600 sec 180 C_MINOFF
STRIKE CLEAR TIME Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S
COOL STAGEUP TIME Cool Stage Increase Time 120 to 999 sec 450 CSTAGINC
COOL SATTREND LEV Cooling SAT Trend Level –1.0 to 1.0 –0.2 SAT_TLC
UPPER MIN SAT Cool Min SAT Upper Level 35.0 to 65.0 °F
53 (sizes 07-12)
56 (sizes 04-06, 14-
26)
SATMIN_H
LOWER MIN SAT Cool Min SAT Lower Level 35.0 to 65.0 °F
42 (sizes 07-12)
46 (sizes 04-06, 14-
26)
SATMIN_L
SPRH DEADBAND Space RH Deadband 0 % 5 SPRH_DB
HUMZ LOCKOUT OAT Humidimizer Lockout Temp –20 to 75 °F 40 OATLHUMZ
HUMZ ENABLE Humidimizer Equipped Yes/No
No: no Humidi-Mizer
FIOP
Yes: Humidi-Mizer
FIOP
HUMZ_EN
COOL FANOFF DELAY Cooling Fan-off Delay 0 to 600 sec 75 COOL_FOD
FBD CONTROL TYPE Fan Based Dehum Type
0=NONE,
1=Comfort,
2=Max
0=NONE FBD_TYPE
FBD LOW SP FBDH Low Set Point –20 to 0 °F delta –2.5 FBDLO_SP
FBD SST SETPOINT FBDH Max Mode SST SP 20 to 60 °F 38 FBDSSTSP
FBD SST MIN VALUE FBDH Min SST Threshold 10 to 60 °F 32 FBDH_SST
FBD COMFORT SAT FBDH Comfort SAT SP 35 to 80 °F 46 FBDH_SAT
FBDSAT COMF DELTA FBD Comfort SAT Delta 0 to 40 °F 11 FBDSATDT
FBD MIN IDF SPEED Minimum IDF Speed 0 to 100 % 25 FBDMINSP
FBD MAX IDF SPEED FBD Fan Max 0 to 100 % 100 FBDFMAX
LOW AMBIENT LOW AMBIENT CONFIGS MENU
CIR.A LOCKOUT OAT Circuit A Lockout Temp –20 to 75 °F
0: no Economizer
FIOP
40: Economizer FIOP
OATLCMPA
LOW AMBIENT TEMP Low Ambient Temperature 0 to 80 °F 66 LA_TEMP
LOW COOL MIN OAT Low Cool lockout Temp –20 to 60 °F
10 (sizes 04-06)
30 (sizes 07-12)
40 (sizes 14-26)
LCLOCKSP
MED COOL MIN OAT Medium Cool lockout Temp –20 to 60 °F
20 (sizes 04-12)
30 (sizes 14-26)
MCLOCKSP
LA DEHUM LEV 1 Low Ambient Dehum Lev 1 40 to 125 °F 80 LAHTEMP1
LA DEHUM LEV 2 Low Ambient Dehum Lev 2 40 to 125 °F 61 LAHTEMP2
Table B — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY