EasyManua.ls Logo

Carrier 48LC Series - Page 98

Carrier 48LC Series
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
98
INDOOR FAN (cont)
VFD IN REVERSE? IDF VFD Motor In Reverse Yes/No
No (sizes 04-12)
Yes (sizes 14-26)
VFD1MDIR
IDF VFD PARAMETERS Indoor Fan VFD Settings Menu
IDF VFD NOM. HP IDF VFD Motor HP 1 to 26 HP
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
MOTPWRHP
IDF VFD VOLTAGE IDF VFD Motor Volts 50 to 1000 V
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
MOTVOLT
IDF VFD NOM. FREQ IDF VFD Motor Freq. 20 to 400 Hz 60 MOTFREQ
IDF VFD NOM. AMPS IDF VFD Motor Current 0.1 to 40 A
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
MOTCUR
IDF VFD NOM. RPM IDF VFD Motor Nom. RPM 100 to 60000 rpm
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
MOTNOMSP
IDF VFD MIN REF IDF Danfoss Min Ref 0 to 65 Hz 0 MINREF
IDF VFD MAX REF IDF Danfoss Max Ref 0 to 65 Hz 60 MAXREF
VFD ACCEL. TIME IDF VFD Accel. Time 1 to 1800 sec 10 RAMPUP_T
VFD DECEL. TIME IDF VFD Decel. Time 1 to 1800 sec 10 RAMPDN_T
IDF VFD MAX AMPS IDF VFD Max Current 0 to 655.35 A
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
VFD1MAXA
IDF VFD TIMEOUT IDF Danfoss Comm. TO 1 to 600 sec 30 CNT_TOUT
IDF VFD RESET DUR IDF Danfoss Auto Reset 0 to 600 sec 30 ARSTRT_T
VFD RFI FILTER IDF Danfoss RFI Filter On/Off On RFIFILTR
ECONOMIZER Economizer Configurations Menu
ECON INSTALLED? Economizer Installed? Yes/No
No: no FIOP
Yes: FIOP
ECONO
ECON MAX POS Econ Max Damper Position 0 to 100 % 100 DAMPMAX
ECON TRAVEL TIME Economizer Travel Time 5 to 300 sec 150 ECONOTRV
MINIMUM POSITION
CONFIGS
Minimum Position Configurations
Menu
MIN POS@ MAX FAN Econ Min at Max Fan Speed 0 to 100 % 30 MINP_MAX
MIN POS SPEED 1 Min Pos – User Speed 1 0 to 100 % 0 MP_USPD1
MIN POS DAMP 1 Min Pos – User Pos 1 0 to 100 % 0 MP_UPOS1
MIN POS SPEED 2 Min Pos – User Speed 2 0 to 100 % 0 MP_USPD2
MIN POS DAMP 2 Min Pos – User Pos 2 0 to 100 % 0 MP_UPOS2
MIN POS SPEED 3 Min Pos – User Speed 3 0 to 100 % 0 MP_USPD3
MIN POS DAMP 3 Min Pos – User Pos 3 0 to 100 % 0 MP_UPOS3
FREE COOL CONFIGS
Free Cooling Specific
Configurations Menu
LOW COOL SAT SP Low Free Cool SAT Setpnt 40 to 80 °F 65 LCSASP
HIGH COOL SAT SP High Free Cool SAT Setpnt 40 to 80 °F 55 HCSASP
FREE COOL MAX OAT Free Cooling Max OAT 0 to 90 °F 65 MAXFREET
FREE COOL MIN OAT Free Cooling Min Temp -30 to 70 °F 0 MINFREET
Table B — Settings Main Menu Layout (cont)