NOMINAL VOLTAGE
48PD POWER RANGE
UNIT SUPPLY
SIZE V-Ph-Hz Min Max
208/230-3-60 187 253
O5
460-3-60 414 506
208/230-3-60 187 253
06
460-3-60 414 506
Table 8 - Electrical Data - Units Without Optional Convenience Outlet
COMPRESSOR OFM COMBUST IFM POWER SUPPLY
FAN Conv PWR
FLA MOTOR Outlet EXH
RLA LRA Qty (ca) FLA FLA TYPE FLA MCA MOCPI-
STD 5.2 26.3/26.3 40/40
ALT 5.2 26.3/26.3 40/40
16.1 110 1 1.0 0.52 none
STD 5.2 27.7/27.7 40/40
1.4
ALT 5.2 27.7/27.7 40/40
STD 2.6 10.9 15
ALT 2.6 10.9 15
6.2 52 1 0.5 0.30 none
STD 2.6 11.5 15
0.6
ALT 2.6 11.5 15
STD 5.2 29.1/29.1 45/45
ALT 5.2 29.1/29.1 45/45
17.9 110 1 1.5 0.52 none
STD 5.2 30.5/30.5 45/45
1.4
ALT 5.2 30.5/30.5 45/45
STD 2.6 13.2 20
ALT 2.6 13.2 20
7.8 52 1 0.8 0.30 none
STD 2.6 13.8 20
0.6
ALT 2.6 13.8 20
DISCONNECT
SIZE
FLA LRA
26/26 142/142
26/26 142/142
27/27 144/144
27/27 144/144
11 68
11 68
11 69
11 69
28/28 143/143
28/28 143/143
30/30 145/145
30/30 145/145
13 69
13 69
14 70
14 70
Table 9 - Electrical Data - Units With Optional Convenience Outlet
NOMINAL VOLTAGE
48PD POWER RANGE
UNIT SUPPLY
SIZE V-Ph-Hz Min Max
208/230-3-60 187 253
O5
460-3-60 414 506
208/230-3-60 187 253
06
460-3-60 414 506
COMPRESSOR OFM COMBUST. IFM POWER SUPPLY
FAN Conv PWR
FLA MOTOR Outlet EXH
RLA LRA Qty (ca) FLA FLA TYPE FLA MCA MOCPI
STD 5.2 31.1/31.1 45/45
ALT 5.2 31.1/31.1 45/45
16.1 110 1 1.0 0.52 YES
STD 5.2 32.5/32.5 45/45
1.4
ALT 5.2 32.5/32.5 45/45
STD 2.6 13.1 15
ALT 2.6 13.1 15
6.2 52 1 0.5 0.30 YES
STD 2.6 13.7 20
0.6
ALT 2.6 13.7 20
STD 5.2 33.9/33.9 50/50
ALT 5.2 33.9/33.9 50/50
17.9 110 1 1.5 0.52 YES
1.4 STD 5.2 35.3/35.3 50/50
ALT 5.2 35.3/35.3 50/50
- STD 2.6 15.4 20
ALT 2.6 15.4 20
7.8 52 1 0.8 0.30 YES
0.6 STD 2.6 16.0 20
ALT 2.6 16.0 20
DISCONNECT
SIZE
FLA LRA
31/31 147/147
31/31 147/147
33/33 149/149
33/33 149/149
13 70
13 70
14 71
14 71
34/34 148/148
34/34 148/148
35/35 150/150
35/35 150/150
15 71
15 71
16 72
16 72
LEGEND
FLA - Full Load Amps
HACR - Heating, Air Conditioning and Refrigeration
IFM - Indoor (Evaporator) Fan Motor
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Overcurrent Protection
NEC - National Electrical Code
OFM - Outdoor (Condenser) Fan Motor
RLA - Rated Load Amps
t Fuse or Breaker
NOTES:
1. In compliance with NEC requirements for muttimotor and combination toad equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage = 224 + 231 + 226
3
681
3
227
Determine maximum deviation from average voltage.
(AB) 227 224 = 3 v
(BC) 231 227 = 4 v
(AC) 227 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
4
% Voltage Imbalance = 100 x
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
15