APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — OPERATING MODES
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
OPERATING MODES MAINTENANCE DISPLAY
MODE
Control Modes
MODES
SYS System Mode text string SYS_MODE
HVAC HVAC Mode text string HVACMODE
OCC Currently Occupied Yes/No OCCUPIED Forcible
T.OVR Timed Override in Effect Yes/No MODETOVR
LINK Linkage Active Yes/No MODELINK
C.LOC Comp Cool OAT Lockout Yes/No COMPLOCK
H.LOC Heat OAT Lockout Yes/No HEATLOCK
E.LOC Econ Cool OAT Lockout Yes/No ECONLOCK
COOL Cool Mode Diagnostic COOLDIAG
COOL In Cooling Mode? Yes/No IN_COOL
OK.CL OK to Select Cool Mode? Yes/No OK TO COOL
MS.TG Mode Select Timeguard 0 to 999 secs COOLMSTG
OK.EC OK to Use Economizer? Yes/No ECONCOOL
OK.MC OK to Use Compressors? Yes/No MECHCOOL
C.LOC Circuit OAT Lockout Yes/No COMPLOCK
CA.LO Circuit A Lockout Temp 0 to 100 dF OATLCMPA
CB.LO Circuit B Lockout Temp 0 to 100 dF OATLCMPB
CC.LO Circuit C Lockout Temp 0 to 100 dF OATLCMPC
AVL.C Available Cooling x AVLCSTGS
REQ.C Requested Cooling x REQCSTGS
ACT.C Actual Compressors x ACTCSTGS
CMP.A Circuit A Compressors On/Off COMP_A
CMP.B Circuit B Compressors On/Off COMP_B
CMP.C Circuit C Compressors On/Off COMP_C
ST.A Circuit A Strikes x ASTRIKES
ST.B Circuit B Strikes x BSTRIKES
ST.C Circuit C Strikes x CSTRIKES
F.LEV Outdoor Fan Level x FANLEV
SAT Supply Air Temperature
SAT Supply Air Temperature xxx.x dF SAT
SA.DM Supply Air Temp Demand xxx.x ^F SAT_DMD
SA.PD SAT Cool Demand (+) Level xx.x ^F SAT_POS
SA.ND SAT Cool Demand (–) Level xx.x ^F SAT_NEG
SAT.U Minimum SAT Upper Level xx.x dF SATMIN_H
SAT.L Minimum SAT Lower Level xx.x dF SATMIN_L
SA.TR Supply Air d/dt (F/min) xxxx.x SAT_TREND
SA.DR SAT Delta Reference Temp xxx.x dF SAT_REF
SPT Space Temperature
SPT Space Temperature xxx.x dF SPACE_T Forcible
DMD.C Cooling Demand xxx.x ^F COOL_DMD
TRD.C Cool Demand d/dt (F/min) xxx.x CLDTREND
CL.PD SPT Cool Demand (+) Level xx.x ^F DEM_POS
CL.ND SPT Cool Demand (–) Level xx.x ^F DEM_NEG
C.LAG Cool Thermal Lag Factor x.x min COOL_LAG
HMZR Humidimizer HUMIDIMIZER
REHT Humidimizer Equipped Yes/No REHEAT
HUM Space Humidity Switch High/Low HUM_STAT Forcible
SP.RH Space Humidity Sensor xxx.x % SPRH Forcible
R.LO.A Reheat2 OAT Lockout A Yes/No RHALOCK
RA.LO Reheat2 OAT Limit A xx F OATLRH_A
R.LP.A Reheat2 SSP Override A Yes/No RHALPOV
R.LO.B Reheat2 OAT Lockout B, C Yes/No RHBLOCK
RB.LO Reheat2 OAT Limit B, C xx F OATLRH_B
R.LP.B Reheat2 SSP Override B, C Yes/No RHBLPOV
AVL.R Available Reheat2 Stages x AVLRSTGS
REQ.R Requested Reheat2 Stages x REQRSTGS
ACT.R Actual Reheat2 Stages x ACTRSTGS
CRC Cool
−>Reheat1 Control On/Off CRC
RH2.A Reheat2 Valve A On/Off RH2_A
RH2.B Reheat2 Valve B, C On/Off RH2_B
HEAT Heat Mode Diagnostic HEATDIAG
HEAT In Heating Mode? Yes/No IN_HEAT
OK.HT OK to Select Heat Mode? Yes/No OK TO HEAT
MS.TG Mode Select Timeguard 0 to 999 secs HEATMSTG
H.LOC Heat OAT Lockout Yes/No HEATLOCK
HT.LO Heating Lockout Temp 40 to 125 F dF OATLHEAT
AVL.H Available Heating Stages x AVLHSTGS
REQ.H Requested Heating Stages x REQHSTGS
ACT.H Actual Heating Stages x ACTHSTGS
HT.1 Heat Stage 1 Relay On/Off HEAT_1
HT.2 Heat Stage 2 Relay On/Off HEAT_2
SPT Space Temperature
SPT Space Temperature xxx.x dF SPACE_T Forcible
DMD.H Heating Demand xxx.x ^F HEAT_DMD
TRD.H Heat Demand d/dt (F/min) xxx.x HTDTREND
HT.PD SPT Heat Demand (+) Level xx.x ^F HDEM_POS
HT.ND SPT Heat Demand (–) Level xx.x ^F HDEM_NEG
H.LAG Heat Thermal Lag Factor x.x min HEAT_LAG