CONTROL SET POINT AND CONFIGURATION LOG
Model Number: ________________________________________ Software Versions: _______________________________________
Serial Number: ________________________________________ MBB: CESR131320-- __ __
Date: ________________________________________ ECB: CESR131249-- __ __
Technician: ________________________________________ MARQ: CESR131171-- __ __
INDICATE UNIT SETTINGS BELOW
Control Type: Thermostat / T-55 Space Temp. / T-56 Space Temp. / T-58 Space Temp.
Set Points: Cooling Occupied: _____________ Unoccupied: ______________
Heating Occupied:_____________ Unoccupied: ______________
MODE — CONFIGURATION
LEGEND
FIOP — Factory-Installed Option
ITEM EXPANSION RANGE DEFAULT ENTRY
CONFIGURATION
DISP Display Configuration
METR Metric Display On/Off Off
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0
PROT Password Enable Enable/Disable Enable
PSWD Service Password 0000 to 9999 1111
TEST Test Display LEDs On/Off Off
UNIT Unit Configuration
S.DLY Start Up Delay 0 to 600 sec 30
U.CTL Unit Control Type 1=Auto Select
2=Thermostat
3=Space Sensor
1
T.CTL Thermostat Control Type 0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
0
OC.FN Fan On When Occupied Yes/No Yes
IDF.F Shut Down on IDF Failure Yes/No Yes
EC.EN Economizer Installed Yes/No No: no FIOP
Yes: FIOP
FN.SW Fan Status Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
FL.SW Filter Status Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
FS.SW Fire Shutdown Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
RM.SW Remote Occupancy Switch 0=No Switch
1=Normally Open
2=Normally Closed
0
SAT.T SAT Settling Time 10 to 900 sec 240
SAT.H SAT Heat Mode Sensing Enable/Disable Disable
RAT.S RAT Sensor On SPTO Input Yes/No No
RH.S RH Sensor ON OAQ Input Yes/No No
RH.SW Space Humidity Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no Humidi-MiZer FIOP
1: Humidi-MiZer FIOP
TCS.C Temp Cmp Strt Cool Factr 0 to 60 mins 0
TCS.H Temp Cmp Strt Heat Factr 0 to 60 mins 0
COOL Cooling Configuration
N.CIR Number of Circuits 1 to 3 2
N.A Compressors on Circuit A 1 to 2 1
MRT.C Compressor Min On Time 120 to 999 sec 180
MOT.C Compressor Min Off Time 300 to 999 sec 300
RST.C Runtime to Reset Strikes 120 to 999 sec 300
C.DEC Cool Stage Decrease Rate 120 to 999 sec 300
C.INC Cool Stage Increase Rate 120 to 999 sec 450
FOD.C Fan-off Delay, Mech Cool 0 to 600 sec 60
CA.LO Circuit A Lockout Temp 0 to 100 dF 0
CB.LO Circuit B Lockout Temp 0 to 100 dF 0: no Humidi-MiZer FIOP
Humidi-MiZer FIOP:
0
CC.LO Circuit C Lockout Temp 0 to 100 dF 0
ALM.N Alert Each Strike Yes/No Yes