Table 30 — ACH550/580 VFD Parameters, for 40RU Units with I/O Flex Controls
VFD PARAMETERS
(ACH550 / ACH580)
PKG ABB ACH550 MOTOR PART NUMBER
VFD PART NUMBER
(ACH550 / ACH580)
DRIVE HP DESC
40RU000205-DATA /
40RU000606-DATA
40RU000205 HD56FR579
HK30WA360 /
HK30WB340
3 40RU 1.7 HP 575V
40RU000220-DATA /
40RU000608-DATA
40RU000220 HD56FE577
HK30WA360 /
HK30WB340
3 40RU 2.4 HP 575V
40RU000225-DATA /
40RU000609-DATA
40RU000225 HD58FE577
HK30WA361 /
HK30WB341
5 40RU 3.7 HP 575V
40RU000208-DATA /
40RU000607-DATA
40RU000208 HD58FE577
HK30WA361 /
HK30WB341
5 40RU 3.7 HP 575V
Table 30 — ACH550/580 VFD Parameters, for 40RU Units with I/O Flex Controls (cont)
LOOKUP VARIABLE N. AMPS N. HP MAX AMPS CROSS REFERENCE
VFD PARAMETERS 9906 / 99.06 9909 / 99.10 2003 / 30.17 EM_PKG CL_PKG
40RU000205-DATA /
40RU000606-DATA
2.8 1.7 3.2 40RU480132
40RU000220-DATA /
40RU000608-DATA
3.8 2.4 4.4 40RU480013
40RU000225-DATA /
40RU000609-DATA
4.9 3.7 5.6 40RU480018
40RU000208-DATA /
40RU000607-DATA
4.5 3.7 5.2 40RU480135
LEGEND
= HVAC Default, field does not require change.

Related product manuals