Table 31 — ACH550/580 VFD Common Parameters for 48/50 Units with ComfortLink Controls
PARAMETERS
ACH550/580
DESCRIPTION
SETTING
ACH550/580
9802 / 58.01 COMM PROT SEL 6 LEN / 8 LEN
9907 / 99.08 Motor Nominal Frequency 60Hz
1001 / 20.01 EXT1 Commands
1102 / 19.11 EXT1/EXT2 Sel
1103 / 28.11 REF 1 Select
1201 / 28.22 Const Speed Sel
1202 / 28.26 Const Speed 1
1203 / 28.27 Const Speed 2
1204 / 28.28 Const Speed 3
1205 / 28.29 Const Speed 4
1401 / 10.24 Relay Output 1
1403 / 10.30 Relay Output 3
1501 / 13.12 AO1 Content Sel
1601 / 20.40 RUN ENABLE
2007 / 30.13 Minimum Frequency
2008 / 30.14 Maximum Frequency
2101 / 21.19 Start FCN
2102 / 21.03 Stop FCN
2201 / 28.71 ACCEL/DECEL
2202 / 28.72 ACCEL
2203 / 28.73 DECEL
2606 / 97.01 Switching Freq
5101 / 51.01 FBA Type
5201 / 58.03 Station ID
5202 / 58.04 Baud Rate
5203 / 58.05 Parity
5301 / 58.25 EFB Protocol ID 0601 hex / NA
5302 / 58.03 EFB Station ID 41
5303 / 58.04 EFB Baud Rate 38.4 kb/s
5304 / 58.05 EFB Parity 8 NONE 1
5305 / 58.25 EFB CTRL Profile DCU PROFILE / ABB Drives