Table 31 — ACH550/580 VFD Common Parameters for 48/50 Units with ComfortLink Controls
PARAMETERS
ACH550/580
DESCRIPTION
SETTING
ACH550/580
9802 / 58.01 COMM PROT SEL 6 LEN / 8 LEN
9907 / 99.08 Motor Nominal Frequency 60Hz
1001 / 20.01 EXT1 Commands —
1102 / 19.11 EXT1/EXT2 Sel —
1103 / 28.11 REF 1 Select —
1201 / 28.22 Const Speed Sel —
1202 / 28.26 Const Speed 1 —
1203 / 28.27 Const Speed 2 —
1204 / 28.28 Const Speed 3 —
1205 / 28.29 Const Speed 4 —
1401 / 10.24 Relay Output 1 —
1403 / 10.30 Relay Output 3 —
1501 / 13.12 AO1 Content Sel —
1601 / 20.40 RUN ENABLE —
2007 / 30.13 Minimum Frequency —
2008 / 30.14 Maximum Frequency —
2101 / 21.19 Start FCN —
2102 / 21.03 Stop FCN —
2201 / 28.71 ACCEL/DECEL —
2202 / 28.72 ACCEL —
2203 / 28.73 DECEL —
2606 / 97.01 Switching Freq —
5101 / 51.01 FBA Type —
5201 / 58.03 Station ID —
5202 / 58.04 Baud Rate —
5203 / 58.05 Parity —
5301 / 58.25 EFB Protocol ID 0601 hex / NA
5302 / 58.03 EFB Station ID 41
5303 / 58.04 EFB Baud Rate 38.4 kb/s
5304 / 58.05 EFB Parity 8 NONE 1
5305 / 58.25 EFB CTRL Profile DCU PROFILE / ABB Drives
LEGEND
— = HVAC Default, field does not require change.