EasyManua.ls Logo

Carrier 48TF004-007 - Electrical Data (Without Convenience Outlet)

Carrier 48TF004-007
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Table 2A — Electrical Data (Without Convenience Outlet)
LEGEND
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.
3. For units with power exhaust: If a single power source is to be used, size wire to include
power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is pow-
ered through the unit (must be in accordance with NEC and/or local codes). Determine
the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 48TF006---5 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change.
The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP
is acceptable. If MCA New is larger than the published MOCP, raise the MOCP to the
next larger size. For separate power, the MOCP for the power exhaust will be 15 amps
per NEC.
UNIT
NOMINAL
VO LTAG E
IFM
TYPE
VOLTAG E
RANGE
COMPR
(ea)
OFM
(ea)
IFM
COMBUSTION
FAN MOTOR
FLA
POWER SUPPLY
DISCONNECT
SIZE*
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
48TF,TM004
(3 Tons)
208/230-1-60
Std
187 254 16.2 96.0
1
/
4
1.4
3.5
.6
25.2/25.2 30/30 24/24 106/106
Alt 4.9 26.6/26.6 35/35 26/26 111/111
208/230-3-60
Std
187 254 10.2 75.0
1
/
4
1.4
3.5
.6
17.7/17.7 25/25 17/17 85/ 85
Alt 4.9 19.1/19.1 25/25 19/19 90/ 90
High 5.2 19.4/19.4 25/25 19/19 109/109
460-3-60
Std
414 508 4.4 40.0
1
/
4
0.8
1.3
.3
7.6 15 7 44
Alt 2.1 8.4 15 8 48
High 2.6 8.9 15 9 57
575-3-60
Std
518 632 3.7 31.0
1
/
4
0.8
1.3
.3
5.5 15 6 35
Alt 2.1 6.0 15 7 37
High 2.6 6.3 15 7 56
48TF,TM005
(4 Tons)
208/230-1-60
Std
187 254 23.3 118.0
1
/
4
1.4
3.5
.6
34.0/34.0 40/40 32/32 129/129
Alt 4.9 35.4/35.4 45/45 34/34 133/133
208/230-3-60
Std
187 254 15.4 90.0
1
/
4
1.4
3.5
.6
24.2/24.2 30/30 23/23 101/101
Alt 4.9 25.6/25.6 30/30 25/25 105/105
High 5.2 25.9/25.9 30/30 25/25 124/124
460-3-60
Std
414 508 8.3 45.0
1
/
4
0.8
1.8
.3
13.0 20 13 51
Alt 2.1 13.3 20 13 53
High 2.6 13.8 20 13 62
575-3-60
Std
518 632 6.4 36.0
1
/
4
0.8
1.8
.3
9.2 15 10 41
Alt 2.1 9.3 15 10 42
High 2.6 9.7 15 10 49
48TF,TM006
(5 Tons)
208/230-1-60
Std
187 254 28.8 147.0
1
/
4
1.4
5.9
.6
43.3/43.3 60/60 42/42 161/161
Alt 6.6 44.0/44.0 60/60 42/42 184/184
208/230-3-60
Std
187 254 16.0 114.0
1
/
4
1.4
5.9
.6
27.3/27.3 35/35 27/27 128/128
Alt 5.2 26.6/26.6 35/35 26/26 148/148
High 7.5 28.9/28.9 35/35 29/29 174/174
460-3-60
Std
414 508 7.4 64.0
1
/
4
0.8
3.1
.3
13.2 20 13 71
Alt 2.6 13.5 20 13 81
High 3.4 13.5 20 13 93
575-3-60
Std
518 632 6.2 52.0
1
/
4
0.8
3.1
.3
9.7 15 11 58
Alt 2.6 9.9 15 11 65
High 3.4 9.9 15 11 76
48TF007
(6 Tons)
208/230-3-60
Std
187 254 20.6 146.0
1
/
4
1.4
5.2
.6
32.4/32.4 40/40 31/31 180/180
High 7.5 34.7/34.7 40/40 34/34 205/205
460-3-60
Std
414 508 9.5 73.0
1
/
4
0.9
2.6
.3
15.4 20 15 90
High 3.4 16.2 20 16 103
575-3-60
Std
518 632 7.6 58.4
1
/
4
0.6
2.6
.3
11.4 15 12 75
High 3.4 11.9 15 13 86
48TM007
(6 Tons)
208/230-3-60
Std
187 254 20.6 146.0
1
/
4
1.4
5.2
.6
32.4/32.4 40/40 31/31 180/180
High 7.5 34.7/34.7 40/40 34/34 205/205
460-3-60
Std
414 508 9.5 73.0
1
/
4
0.9
2.6
.3
15.4 20 15 90
High 3.4 16.2 20 16 103
575-3-60
Std
518 632 7.6 58.4
1
/
4
0.6
2.6
.3
11.4 15 12 79
High 3.4 11.9 15 13 86
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
% Voltage Imbalance = 100 x
7
457
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
POWER EXHAUST
PA R T N O.
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
MOCP
(for separate
power source)
CRPWREXH030A00
1.6 N/A 0.64 15
CRPWREXH021A00
N/A 0.9 N/A 15
CRPWREXH022A00
3.3 N/A 1.32 15
CRPWREXH023A00
N/A 1.8 N/A 15
CRPWREXH028A00
1.7 N/A 0.68 15
CRPWREXH029A00
N/A 1.0 N/A 15

Table of Contents

Related product manuals