Table 9 Fan Performance, 48TJD/TJE/TJF006 Vertical Discharge Units;
Standard Motor (Direct)
AIRFLOW
(Cfm)
LOW SPEED MEDIUM SPEED HIGH SPEED
208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v
Esp Watts Esp Watts Esp Watts Esp Watts Esp Watts Esp Watts
1500 0.69 750 1.01 791 1.00 782 1.20 845 1.22 875 1.28 949
1600 0.49 780 0.85 824 0.85 821 1.06 883 1.09 913 1.17 988
1700 0.29 810 0.70 857 0.70 861 0.93 921 0.97 950 1.06 1027
1800 0.09 839 0.54 891 0.55 900 0.80 959 0.84 988 0.95 1066
1900 0.39 924 0.40 940 0.67 997 0.72 1025 0.84 1105
2000 0.23 957 0.25 979 0.54 1035 0.59 1063 0.73 1144
2100 0.08 990 0.10 1018 0.41 1073 0.46 1101 0.62 1183
2200 0.28 1111 0.34 1138 0.51 1222
2300 0.15 1149 0.21 1176 0.40 1261
2400 0.02 1187 0.09 1213 0.29 1300
2500 0.18 1340
LEGEND
Esp External Static Pressure (in. wg)
NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. For additional information on motor performance, re-
fer to Table 4.
3. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .67
Table 10 Fan Performance, 48TJD/TJE/TJF006 Vertical Discharge Units;
Alternate Motor (Belt)
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
1500 729 368 788 429 896 572 981 705 1070 869 1144 1032 1226 1216 1301 1492 1380 1757
1600 770 429 826 501 930 654 1015 797 1098 961 1173 1134 1242 1308 1318 1523 1392 1800
1700 811 511 864 582 964 736 1051 899 1124 1053 1203 1237 1270 1420 1335 1615 1408 1850
1800 852 593 903 674 999 838 1085 1001 1155 1155 1231 1349 1300 1553 1361 1747 1423 1952
1900 893 695 942 777 1035 940 1119 1124 1191 1288 1256 1461 1329 1676 1391 1891 1448 2095
2000 935 797 982 889 1070 1063 1153 1247 1227 1431 1287 1604 1355 1809 1420 2034 1477 2258
2100 977 910 1022 1012 1107 1196 1187 1380 1260 1574 1323 1758 1381 1952 1449 2187 1509 2420
2200 1019 1042 1063 1145 1144 1328 1222 1523 1294 1737 1359 1931 1413 2126 1474 2350 1538 2578
2300 1061 1185 1104 1288 1182 1502 1258 1686 1328 1901 1393 2115 1449 2310 1502 2518 1561 2732
2400 1103 1328 1145 1441 1220 1645 1293 1860 1362 2074 1426 2310 1485 2524 1540 2720 1590 2900
2500 1145 1492 1186 1604 1259 1819 1329 2044 1397 2269 1460 2504 1522 2739 1581 2948 1629 3113
NOTES:
1. Boldface indicates a field-supplied drive is required. (See
Note 6.)
2. indicates field-supplied motor and drive are required.
3. Maximum usable watts input is 1921. Extensive motor and elec-
trical testing on these units ensures that the full range of the motor
can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. For ad-
ditional information on motor performance, refer to Table 4.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Alternate motor drive range: 900 to 1300. All other rpms require
field-supplied drive.
7. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .74
22