17
Step 12 Install All Accessories After all the
factory-installed options have been adjusted, install all field-
installed accessories. Refer to the accessory installation
instructions included with each accessory.
MOTORMASTER® I CONTROL INSTALLATION
(48TM016,020, and 028)
Install Field-Fabricated Wind Baffles
Wind baffles must
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 22 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be
1
/
4
-in. diameter and
5
/
8
-in. long. Drill required screw holes for mounting baffles.
Install Motormaster I Controls Only one Motormaster I
control is required for 48TM016 and 020 units. The 48TM028
requires 2 Motormaster I controls one for circuit 1 and
one for circuit 2. The Motormaster I control must be used in
conjunction with the accessory F low ambient kit
(purchased separately). The Motormaster I device controls
outdoor fan no. 1 (and 4 on size 028 units) while outdoor fans
no. 2 and 3 (and 5 and 6 on 028 units) are sequenced off by the
Accessory F Low Ambient Kit.
Accessory F Low Ambient Kit Install the accessory F
low ambient kit per instruction supplied with accessory.
Sensor Assembly Install the sensor assembly in the location
shown in Fig. 23.
Motor Mount To ensure proper fan height, replace the exist-
ing motor mount with the new motor mount provided with
accessory.
Transformer (460 and 575-v Units Only) On 460 and 575-v
units, a transformer is required. The transformer is provided
with the accessory and must be field-installed.
Motormaster I Control Recommended mounting location is
on the inside of the panel to the left of the control box. The
control should be mounted on the inside of the panel, verti-
cally, with leads protruding from bottom of extrusion.
To avoid damage to the refrigerant coils and electrical com-
ponents, use recommended screw sizes only. Use care
when drilling holes.
NOTE: Dimensions in ( ) are in mm.
Fig. 22 Wind Baffle Details
SENSOR
LOCATION
HAIRPIN END
SENSOR
LOCATION
HAIRPIN END
SENSOR
LOCATION
HAIRPIN END
48TM016 48TM020 48TM028
(Circuits 1 and 2)
NOTE: All sensors are located on the eighth hairpin up from the
bottom.
Fig. 23 Motormaster® I Sensor Locations