Unit Dimensions
50BL050, 060, 080
Electrical Data
Model Vols/Ph/Hz
Voltage Range Power SupplyCompressor No: 1 Indoor Fan Motor
Min Max RLA LRA KW FLA MIN. CKT AMIPS MOCP AMPS
50BY008 380/3/50 360 440 13.5 63 0.75 1.9 24.4 35.7
50BY010 380/3/50 360 440 17.7 115 1.50 3.5 29.2 49.2
50BY015 380/3/50 360 440 29.0 115 2.20 4.5 40.8 69.8
50BY020 380/3/50 360 440 38.0 104 3.70 7.9 55.4 93.4
50BY025 380/3/50 360 440 38.0 104 3.70 7.9 55.4 93.4
50BY030 380/3/50 360 440 48.0 134 5.50 10.0 70.0 118.0
50BY040 380/3/50 360 440 76.0 207 7.50 13.0 108.0 184.0
50BL050 380/3/50 360 440 38.0 173 7.50 13.0 108.0 184.0
50BL060 380/3/50 360 440 48.0 223 11.00 21.0 129.0 177.0
50BL080 380/3/50 360 440 76.0 345 15.00 28.0 199.0 275.0
Note:
Unit 50BL050-50BL080 have 2 compressors. Values are for each compressor.
FLA : Full Load Amps LRA : Locked Rotor Amps
RLA : Rated Load Amps MOCP : Maximum Overcurrent Protective Device