SERVICE
A
WARNING
Before
performing
service
or
maintenance
operations
on
unit,
turn
off
main
power
switch
to
unit.
Turn
off
accessory
heater
power
switch
if
applicable.
Elec¬
trical
shock
could
cause
personal
injury.
Cleaning
Inspect
unit
interior
at
beginning
of
each
heating
and
cooling
season
or
as
operating
conditions
require.
Remove
unit
top
panel
and/or
side
panels
for
access
to
unit
interior.
INDOOR
COIL
Clean
with
a
commercial
coil
cleaner.
OUTDOOR
COIL
Clean
outdoor
coil
annually
or
as
required
by
location
or
outdoor
air
conditions.
Inspect
coil
monthly
clean
as
required.
CONDENSATE
DRAINS
—Check
and
clean
each
year
at
start
of
cooling
season.
In
winter,
keep
drains
and
traps
dry
or
protect
against
freeze-up.
FILTERS
Clean
or
replace
at
start
of
each
heating
and
cooling
season,
or
more
often
if
operating
conditions
require.
Refer
to
Table
1
for
type
and
size.
OUTDOOR
AIR
INLET
SCREENS
Clean
screens
with
steam
or
hot
water
and
a
mild
detergent.
Do
not
use
throwaway
filters
in
place
of
screens.
Lubrication
COMPRESSORS
Each
compressor
is
charged
with
correct
amount
of
oil
at
the
factory.
FAN
SHAFT
BEARINGS
No
lubrication
required.
Bearings
are
permanently
lubricated.
FAN
MOTOR
BEARINGS
No
lubrication
of
out¬
door
fan
or
indoor
blower
motors
are
required
for
first
5
years
of
operation.
Annually
thereafter,
clean
and
repack
bearings
with
a
suitable
bearing
grease.
5.
Set
movable
flange
at
nearest
keyway
of
pulley
hub
and
tighten
setscrew.
(See
Table
1
for
speed
change
for
each
full
turn
of
pulley
flange.)
To
align
fan
and
motor
pulleys,
loosen
fan
pulley
set¬
screws
and
slide
fan
pulley
along
fan
shaft.
Make
angular
alignment
by
loosening
motor
from
mounting
plate.
Fig.
21
Indoor
Air
Fan
Pulley
Adjustment
(50DPE014
and
50DP016)
To
Adjust
Belt
Tension
Loosen
fan
motor
pivot
bolts.
Move
motor
mounting
plate
up
or
down
for
proper
belt
tension
(1/2-in.
deflection
with
one
finger)
and
tighten
pivot
bolts.
Adjust
lock
bolt
and
nut
on
mounting
plate
to
secure
in
fixed
position.
Outdoor
Air
Fan
Adjustment
(Fig.
22)
Shut
off
unit
power
supply.
Remove
fan
top
grille
assembly
and
loosen
fan
hub
screws.
Adjust
fan
height
on
unit
using
a
straight
edge
placed
across
the
fan
orifice,
tighten
setscrews
and
replace
rubber
hubcap
to
prevent
hub
from
rusting
to
motorshaft.
Fill
hub
recess
with
permagum
if
rubber
hubcap
is
missing.
Indoor
Air
Fan
Adjustment
Fan
motor
pulleys
are
factory
set
for
speed
shown
in
Table
1.
The
50DP020
units
have
fixed
pulleys.
Fan
speed
can
be
adjusted
only
by
changing
the
pulley.
To
change
fan
speed
on
50DPE014
and
50DP016:
1.
Shut
off
unit
power
supply.
2.
Loosen
belt
by
loosening
fan
motor
mounting
plate
nuts.
3.
Loosen
movable
pulley
flange
setscrew
(see
Fig.
21).
4.
Screw
movable
flange
toward
fixed
flange
to
increase
speed
and
away
from
fixed
flange
to
decrease
speed.
Increasing
fan
speed
increases
load
on
motor.
Do
not
exceed
maximum
speed
specified
in
Table
1.
See
Table
4
for
air
quantity
limits.
Fig.
22
Outdoor
Air
Fan
Adjustment
14