Loading...
25%
ADJUSTABLE
AIR
DAMPER
SECURING
SCREWS
BASE
UNIT
Fig.
12
25%
Outdoor
Air
Section
Details
COOLING
LOCKOUT
SWITCH
ENTHALPY
CONTROL
DAMPER
MOTOR
FILTERS
ECONOMIZER
CONTROL
BOX
ECONOMIZER
DAMPER
ASSEMBLY
Fig.
14
Enthalpy
Control
Assembly
Mixed
Air
Thermostat
Setting
Set
mixed
air
thermo¬
stat
in
return
air
compartment
to
desired
temperature
of
air
delivered
to
the
conditioned
space
(not
less
than
35
F
or
condensation
in
unit
will
result).
Damper
Vent
Position
Setting
1.
Set
fan
switch
at
ON
(continuous
fan
operation)
and
close
night
switch
if
used.
2.
Set
system
selector
switch
to
OFF.
3.
Remove
cap
from
vent
adjustment
screw
on
damper
motor
terminal
box
cover.
4.
Turn
adjustment
screw
slowly
until
dampers
assume
desired
vent
position.
Do
not
manually
operate
damper
motor;
damage
to
motor
will
result.
Fig.
13
Enthalpy
Control
Location
(Economizer
Damper
Assembly
End
View)
8