110
APPENDIX D: SystemVut Controller CCN Tables
Service Config Tables (cont)
TABLE DISPLAY NAME VALUES UNITS POINT NAME WRITE STA TUS
IN_D_CFG
0=None
1=MBBDI12
2=MBBDI13
3=MBBDI14
4=MBBDI02
5=MBBY3
COFS Assigned Channel 0to5 COFSCHAN 0: No FIOP
4: FIOP
Remote Occupancy Channel 0to5 RMOCCHAN 0 = NONE
Remote Shutdown Channel 0to5 ROFFCHAN 0 = NONE
Filter Status Sw Channel 0to5 FILTCHAN 0: No FIOP
1: FIOP
Enthalpy Sw Channel 0to5 ENTHCHAN 0 = NONE
General Status Channel 0to5 GEN_CHAN 0 = NONE
Humidistat Status Chan. 0to5 HUMDCHAN 0 : N o H u m i d i --- M i Z e r F I O P
5 : H u m i d i --- M i Z e r F I O P
IAQ override sw channel 0to5 IAQOCHAN 0 = NONE
Fan Status Channel 0to5 FNSTCHAN 0 = NONE
Phase Monitor Channel 0to5 PMR_ CHAN 0: no FIOP
3: FIOP
0 = Normally Open
1 = Normally Closed
COFS Switch Type 0to1 COFS_ CFG 0=NORMCLSD
Remote Occupancy Sw Type 0to1 RMOC_CFG 0=NORMOPEN
Remote Shutdown SW Type 0to1 ROFF_CFG 0=NORMOPEN
Filter Status Swith Type 0to1 FILT_CFG 0=NORMOPEN
Enthalpy Switch Type 0to1 ENTH_CFG 0=NORMOPEN
General Status Sw Type 0to1 GENS_CFG 0=NORMOPEN
Humidistat Switch Type 0to1 HUMD_CFG 0=NORMOPEN
IAQ Override Switch Type 0to1 IAQOSCFG 0=NORMOPEN
Fan Status SW Type 0to1 FANSTCFG 0=NORMOPEN
Phase Monitor SW Type 0to1 PMR_CFG 0=NORMCLSD
General Status shutdown? Yes/No GENFATAL Yes
0=Normal
1=Emergency
Remote Shutdown ALM Type 0to1 ROFFTYPE 0=NORMAL
0 = Normally Open
1 = Normally Closed
2=NoSwitch
Fire Shutdown Switch 0to2 FIRE_CFG 2: no FIOP
0: FIOP
IN_A_CFG
0=None
1=MBBAI06
2=MBBAI07
3=MBBAI08
IAQ Assigned Channel 0to3 IAQ_CHAN 0: No FIOP
2: FIOP
OAQ Assigned Channel 0to3 OAQ_CHAN 0 = NONE
OARH Assigned Channel 0to3 OARHCHAN 0: no FIOP
3: FIOP
RARH Assigned Channel 0to3 RARHCHAN 0 = NONE
SPRH Assigned Channel 0to3 SPRHCHAN 0 = NONE
OACFM Assigned Channel 0to3 OCFMCHAN 0 = NONE
SPRH Sensor V alue at 4mA 0 to 100 % SPRH_4MA 0
SPRH Sensor V alue @ 20mA 0 to 100 % SPRH20MA 100
IAQ Sensor Value at 4mA 0 to 5000 PPM IAQ_ 4MA 0
IAQ Sensor Value at 20mA 0 to 5000 PPM IAQ_20MA 2000
OAQ Sensor Value at 4mA 0 to 5000 PPM OAQ_4MA 0
OAQ Sensor Value at 20mA 0 to 5000 PPM OAQ_20MA 2000
OARH Sensor Value at 4mA 0 to 100 % OARH_4MA 0