4 - INFORMATION ABOUT THE UNIT STATUS
Unit status screens
The main parameters of the regulation are displayed in this group
of screens.
They can be accessed in two ways:
- By pressing the
key from the initial screen.
- By pressing the
key from the initial screen, the MAIN MENU
is accessed. This is the group of screens F. MODES. Press the
key to enter the group.
U01: This indicates the number of the unit in which the terminal is
connected.
Ind.T: This indicates the ambient (by default) or return (optional)
air temperature.
Out.T: Outdoor air temperature. In units with humidity probe, this
indicates the relative humidity of the indoor air.
00:00: Time
00/00/00: Date
ES: Language of the terminal screens. The available languages are:
Spanish (ES), French (FR), English (EN) and Italian (IT).
The language of the screens can be selected by pressing the keys
+ at the same time for a few seconds.
00:00: Indicates the time.
WIN / SUM / AL: This indicates the operating status: WINTER
or SUMMER. In the event of alarm, the indication “AL” will appear
alternately.
Indoor T: This indicates the ambient (by default) or return
(optional) air temperature.
Outdoor T: This indicates the outdoor air temperature.
00:00 and 00/00/0000: This indicates the time and date.
WIN / SUM / AL: Operating mode.
Active temp.: Setpoint temperature.
Unit: This indicates the OFF/ON status.
Machine status: Available options status (e.g. Fcool).
LIMIT: This text appears intermittently when the control of the
supply temperature is activated
Supervisory: Type of protocol.
Address: in the supervision network. This could be di erent from
the board address.
Baud rate: Bit rate (38400, 19200, 9600, 4800, 2400, 1200).
P01
Unit:01 00:00 WIN
Indoor T: 00.0ßC
Outdoor T: 00.0ßC
Indoor RH: 00.0%
Unit On Fcool
COMP VENT EL-H LIMIT
P02
00:00 00/00/0000 WIN
Control setpoint
Active temp.: 00.0ßC
Unit On Fcool
LIMIT
P03
Unit: 01
Supervisory: CAREL
Address: 001
Baud rate: 19200
Indoor RH: This indicates the relative humidity of the indoor air (in
units with return or ambient humidity probe, optional).
Unit: This indicates the OFF/ON status:
On Turned on.
Off Turned o .
Remote Off If enabled for a remote shutdown.
Off by phase If the unit is shut down by Scheduling.
Machine status: Available options status:
Fcool Active free-cooling.
Comp Active compressors in summer in addition to free-cooling.
Deum Dehumidifi cation.
Gas Gas burner/boiler operating above the minimum.
COMP VENT EL-H: The meaning of these texts on the display is:
compressor (COMP), supply fan (VENT) and electrical heaters
(RES) in operation.
LIMIT: This text appears intermittently when the control of the
supply temperature is activated, limiting the capacity of the unit.
Initial screen
When the Graphic terminal is switched on, the screen below shows
this information:
On the second screen of the group is shown:
The next screen of the group only appears when the unit is integrated
in a pLAN or supervision network (Carel, Konnex, Bacnet Ethernet,
Bacnet MSTP, Ethernet and Modbus RTU protocols).
Congig. unidad P04
50FC0062
AIR-AIR Rev. Heat Pump
4 Comp/2 Circ
Double vol. electronic
Refrigerant R410A
WO No.: 12345678
The last screen reports on the confi guration of the unit.
NßWO
: Work order number of the unit (needed in case of consultation
with the Technical Support Service).
U01 Ind.T: 00.0ßC
Out.T: 00.0ßC
00:00 EN 00/00/00
G
H
F
Main menu 06/15
MODES
GENCONFIG
SERCONFIG
The fi rst screen of this group collects the following information: