Parameters of “Clock/Scheduler” (...continuation)
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
PH05 M_PAR_2C
Stop minute of slot 3 - program 2
0 0 59 min Integer R/W
97
PH06 H_ARR_3A
Start-up hour of slot 1 - program 3
7 0 23 h Integer R/W
98
PH06 M_ARR_3A
Start-up minute of slot 1 - program 3
0 0 59 min Integer R/W
99
PH06 H_PAR_3A
Stop hour of slot 1 - program 3
15 0 23 h Integer R/W
100
PH06 M_PAR_3A
Stop minute of slot 1 - program 3
0 0 59 min Integer R/W
101
PH06 H_ARR_3B
Start-up hour of slot 2 - program 3
0 0 23 h Integer R/W
102
PH06 M_ARR_3B
Start-up minute of slot 2 - program 3
0 0 59 min Integer R/W
103
PH06 H_PAR_3B
Stop hour of slot 2 - program 3
0 0 23 h Integer R/W
104
PH06 M_PAR_3B
Stop minute of slot 2 - program 3
0 0 59 min Integer R/W
105
PH06 H_ARR_3C
Start-up hour of slot 3 - program 3
0 0 23 h Integer R/W
106
PH06 M_ARR_3C
Start-up minute of slot 3 - program 3
0 0 59 min Integer R/W
107
PH06 H_PAR_3C
Stop hour of slot 3 - program 3
0 0 23 h Integer R/W
108
PH06 M_PAR_3C
Stop minute of slot 3 - program 3
0 0 59 min Integer R/W
109
PH07 SET_INT_FRIO
Schedule only setpoint change: internal Set in summer
26.0 -99.9 99.9 °C Analog. R/W
61
PH07 SET_EXT_FRIO
Schedule only setpoint change: external Set in summer
28.0 -99.9 99.9 °C Analog. R/W
59
PH08 SET_INT_CALOR
Schedule only setpoint change: internal Set in winter
21.0 -99.9 99.9 °C Analog. R/W
60
PH08 SET_EXT_CALOR
Schedule only setpoint change: external Set in winter
19.0 -99.9 99.9 °C Analog. R/W
58
PH09 SET_INT_LIM_FRIO
ON/OFF schedule with limit SET of ON (summer): internal Set
26.0 -99.9 99.9 °C Analog. R/W
79
PH09 SET_EXT_LIM_FRIO
ON/OFF schedule with limit SET of ON (summer): limit Set
34.0 -99.9 99.9 °C Analog. R/W
77
PH10 SET_INT_LIM_CALOR
ON/OFF schedule with limit SET of ON (winter): internal Set
21.0 -99.9 99.9 °C Analog. R/W
78
PH10 SET_EXT_LIM_CALOR
ON/OFF schedule with limit SET of ON (winter): limit Set
13.0 -99.9 99.9 °C Analog. R/W
76
PH11 DIF_LIM_CALOR
ON/OFF schedule with limit SET of ON (winter): di erential
1.0 0.0 99.9 °C Analog. R/W
81
PH11 DIF_LIM_FRIO
ON/OFF schedule with limit SET of ON (summer): di erential
2.0 0.0 99.9 °C Analog. R/W
80
PH12 LUN_A
Monday schedule (0 = o ; 1 = prog. 1; 2 = prog. 2; 3 = prog. 3)
1 0 3 --- Integer R/W
110
PH12 MAR_A
Tuesday schedule (0 = o ; 1 = prog. 1; 2 = prog. 2; 3 = prog. 3)
1 0 3 --- Integer R/W
111
PH12 MIE_A
Wednesday schedule (0 = o ; 1 = prog. 1; 2 = prog. 2; 3 = prog. 3)
1 0 3 --- Integer R/W
112
PH12 JUE_A
Thrusday schedule (0 = o ; 1 = prog. 1; 2 = prog. 2; 3 = prog. 3)
1 0 3 --- Integer R/W
113
PH12 VIE_A
Friday schedule (0=o ; 1=program1; 2=program2; 3=program3)
3 0 3 --- Integer R/W
114
PH12 SAB_A
Saturday schedule (0 = o ; 1 = prog. 1; 2 = prog. 2; 3 = prog. 3)
0 0 3 --- Integer R/W
115
PH12 DOM_A
Sunday schedule (0 = o ; 1 = prog. 1; 2 = prog. 2; 3 = prog. 3)
0 0 3 --- Integer R/W
116
PH12 DIA_SEMANA
Weekday
0 0 0 day Integer R/W
52
PH13 Scheduler_1.Day Programming day 0 0 6 --- Integer R/W
PH13 Scheduler_1.CopyTo_Day Copy day 0 0 7 --- Integer R/W
PH13 Scheduler_1.EnDayCopy Enabling copy 0 0 1 --- Digital R/W
PH13 Scheduler_1.Event_Msk[0].Enabled Daily event enabled 0 0 1 --- Digital R/W
PH13 Scheduler_1.Event_Msk[0].Hours Start time of the daily event 0 0 23 --- Integer R/W
PH13 Scheduler_1.Event_Msk[0].Mins Starting minute of the daily event 0 0 59 --- Integer R/W
PH13
Scheduler_1.Event_Msk[0].
UnitStatus
Daily event unit status (0=OFF; 1=PROTECTION; 2=ECONOMY;
3=COMFORT)
0 0 3 --- Integer R/W
PH13 Scheduler_1.Event_Msk[1].Enabled Daily event enabled 0 0 1 --- Digital R/W
PH13 Scheduler_1.Event_Msk[1].Hours Start time of the daily event 0 0 23 --- Integer R/W
PH13 Scheduler_1.Event_Msk[1].Mins Starting minute of the daily event 0 0 59 --- Integer R/W
PH13
Scheduler_1.Event_Msk[1].
UnitStatus
Daily event unit status (0=OFF; 1=PROTECTION; 2=ECONOMY;
3=COMFORT)
0 0 3 --- Integer R/W
PH13 Scheduler_1.Event_Msk[2].Enabled Daily event enabled 0 0 1 --- Digital R/W
PH13 Scheduler_1.Event_Msk[2].Hours Start time of the daily event 0 0 23 --- Integer R/W
PH13 Scheduler_1.Event_Msk[2].Mins Starting minute of the daily event 0 0 59 --- Integer R/W
PH13
Scheduler_1.Event_Msk[2].
UnitStatus
Daily event unit status (0=OFF; 1=PROTECTION; 2=ECONOMY;
3=COMFORT)
0 0 3 --- Integer R/W
PH13 Scheduler_1.Event_Msk[3].Enabled Daily event enabled 0 0 1 --- Digital R/W
PH13 Scheduler_1.Event_Msk[3].Hours Start time of the daily event 0 0 23 --- Integer R/W
PH13 Scheduler_1.Event_Msk[3].Mins Starting minute of the daily event 0 0 59 --- Integer R/W
PH13
Scheduler_1.Event_Msk[3].
UnitStatus
Daily event unit status (0=OFF; 1=PROTECTION; 2=ECONOMY;
3=COMFORT)
0 0 3 --- Integer R/W
PH13 Scheduler_1.DaysSchedMsg Messages to be displayed for daily events 0 0 9 --- Integer R
PH13 Scheduler_1.SaveData Save data 0 0 1 --- Integer R/W
PH13a
Scheduler_1.VacationsSched[0].
Enabled
Leave period 0 0 1 --- Digital R/W
PH13a
Scheduler_1.VacationsSched[0].
StartDay
First day of the period 0 1 31 --- Integer R/W
PH13a
Scheduler_1.VacationsSched[0].
StartMonth
First month of the period 0 1 12 --- Integer R/W
PH13a
Scheduler_1.VacationsSched[0].
EndDay
Last day of the period 0 1 31 --- Integer R/W
13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
SCHEDULE
L