13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of “Input/Output”
Screen
Parameter Description of the parameter
Value Min. Max. UOM Type R/W
Add.
BMS
I01 TEMP_RET Display of the return air temperature 0.0 -99.9 99.9 °C Analog. R 1
I01 TEMP_EXT Display of the outdoor air temperature 0.0 -99.9 99.9 °C Analog. R 2
I01a TEMP_SONDA_AMB Display of the ambient air temperature (NTC or RS485) 0.0 -99.9 99.9 °C Analog. R
I01a SONDA_AMB_1_TEMP Display of the ambient temperature probe No.1 - RS485 0.0 -99.9 99.9 °C Analog. R 193
I01a SONDA_AMB_2_TEMP Display of the ambient temperature probe No.2 - RS485 0.0 -99.9 99.9 °C Analog. R 196
I01a SONDA_AMB_3_TEMP Display of the ambient temperature probe No.3 - RS485 0.0 -99.9 99.9 °C Analog. R 241
I01a SONDA_AMB_4_TEMP Display of the ambient temperature probe No.4 - RS485 0.0 -99.9 99.9 °C Analog. R 244
I01a SEL_TEMP_SONDAS_AMB_CALOR
Selection of the value of ambient temperature with RS485 probes
in HEATING mode (0 = middle, 1 = minimum, 2 = maximum)
0 0 2 --- Analog. R 200
I01a SEL_TEMP_SONDAS_AMB_FRIO
Selection of the value of ambient temperature with RS485 probes
in COOLING mode (0 = middle, 1 = minimum, 2 = maximum)
0 0 2 --- Analog. R 199
I01b TEMP_TCO Selection of the value of ambient temperature with User terminal 0.0 -99.9 99.9 °C Analog. R 14
I02 HUM_SONDA_INT_RS485_O_AI10 Display of the ambient humidity RS485 probe (middle value) 0.0 -99.9 99.9 %rH Analog. R 5
I02 SONDA_AMB_1_HUM Display of the ambient humidity probe No.1 - RS485 0.0 -99.9 99.9 %rH Analog. R 194
I02 SONDA_AMB_2_HUM Display of the ambient humidity probe No.2 - RS485 0.0 -99.9 99.9 %rH Analog. R 197
I02 SONDA_AMB_3_HUM Display of the ambient humidity probe No.3 - RS485 0.0 -99.9 99.9 %rH Analog. R 242
I02 SONDA_AMB_4_HUM Display of the ambient humidity probe No.4 - RS485 0.0 -99.9 99.9 %rH Analog. R 245
I02a HUM_EXT Display of the outdoor air humidity 0.0 -99.9 99.9 %rH Analog. R 6
I02b Speed_Input_Rpm_FRIO_Fan1 rpm setpoint for control of supply fan in COOING mode 1200 0 2950 rpm Integer R 275
I02b Speed_Input_Rpm_CALOR_Fan1 rpm setpoint for control of supply fan in HEATING mode 1200 0 2950 rpm Integer R 277
I02b Speed_Input_Rpm_VENTIL_Fan1 rpm setpoint for control of supply fan in VENTILATION 1200 0 2950 rpm Integer R 279
I02b CAUDAL_VINT_MEDIDO_AJUSTE Measured ow rate at supply 0 0 99999 m
3/
h Integer R 198
I02b actual_speed_msk_Fan1 Current speed of supply fan 0 0 9999 rpm Integer R 199
I02b SET_CAUDAL_VINT_FRIO Setpoint for constant supply ow control in COOING mode 30600 0 99999 m
3/
h Integer R 200
I02b SET_CAUDAL_VINT_CALOR Setpoint for constant supply ow control in HEATING mode 30600 0 99999 m
3/
h Integer R 201
I02b
SET_CAUDAL_VINT_
VENTILACION
Setpoint for constant supply ow control in VENTILATION 30600 0 99999 m
3/
h Integer R 197
I02b Speed_Input_perc_FRIO_Fan1 % setpoint for PWM control of supply fan in COOING mode 50.0 0.0 100.0 % Analog. R 160
I02b Speed_Input_perc_CALOR_Fan1 % setpoint for PWM control of supply fan in HEATING mode 50.0 0.0 100.0 % Analog. R 161
I02b Speed_Input_perc_VENTIL_Fan1 % setpoint for PWM control of supply fan in VENTILATION 50.0 0.0 100.0 % Analog. R 159
I02c Speed_Input_Rpm_FRIO_Fan2 rpm setpoint for control of return fan in COOING mode 1200 0 2950 rpm Integer R 276
I02c Speed_Input_Rpm_CALOR_Fan2 rpm setpoint for control of return fan in HEATING mode 1200 0 2950 rpm Integer R 278
I02c Speed_Input_Rpm_VENTIL_Fan2 rpm setpoint for control of return fan in VENTILATION 1200 0 2950 rpm Integer R 280
I02c CAUDAL_VRET_MEDIDO_AJUSTE Measured ow rate at return 0 0 99999 m
3/
h Integer R 204
I02c actual_speed_msk_Fan2 Current speed of return fan 0 0 9999 rpm Integer R 205
I02c SET_CAUDAL_VRET_FRIO Setpoint for constant return ow control in COOING mode 30600 0 99999 m
3/
h Integer R 206
I02c SET_CAUDAL_VRET_CALOR Setpoint for constant return ow control in HEATING mode 30600 0 99999 m
3/
h Integer R 207
I02c
SET_CAUDAL_VRET_
VENTILACION
Setpoint for constant return ow control in VENTILATION 30600 0 99999 m
3/
h Integer R 203
I02c Speed_Input_perc_FRIO_Fan2 % setpoint for PWM control of return fan in COOING mode 50.0 0.0 100.0 % Analog. R 175
I02c Speed_Input_perc_CALOR_Fan2 % setpoint for PWM control of return fan in HEATING mode 50.0 0.0 100.0 % Analog. R 176
I02c Speed_Input_perc_VENTIL_Fan2 % setpoint for PWM control of return fan in VENTILATION 50.0 0.0 100.0 % Analog. R 174
I03 TEMP_IMP Display of the supply air temperature 0.0 -99.9 99.9 °C Analog. R 7
I03 TEMP_MEZCLA Display of the mixing air temperature 0.0 -99.9 99.9 °C Analog. R 8
I03a CO2
Display of the CO2 probe or the di󰀨 erence between indoor probe
and outdoor probe (in units with outdoor CO2 probe)
0 -9999 9999 ppm Integer R 3
I03a CO2_FISICA_zona1 Reading of the CO2 probe of zone 1 (zoning into 2 zones) 0 -9999 9999 ppm Integer R 256
I03a CO2_FISICA_zona2
Reading of the CO2 probe of zone 2 (zoning into 2 zones) or
second CO2 probe or outdoor CO2 probe
0 -9999 9999 ppm Integer R 220
I03a1 CO2
Display of the di󰀨 erential pressure sensor reading for air renewal
(Pa)
0 -9999 9999 Pa Integer R 3
I03b TEMP_ENTRADA_BAC Display of the water inlet temperature of the hot water coil 0.0 -99.9 99.9 °C Analog. R 25
I03b TEMP_SALIDA_BAC Display of the water outlet temperature of the hot water coil 0.0 -99.9 99.9 °C Analog. R 26
I03c TEMP_EXTRACCION_RUEDA Display of the exhaust air temperature on the wheel 0.0 -99.9 99.9 °C Analog. R 247
I03c TEMP_RECUPERACION_RUEDA Display of the recovery air temperature on the wheel 0.0 -99.9 99.9 °C Analog. R 249
I04a ENTALPIA_EXT_KCAL Display of the outdoor enthalpy 0.0 -99.999 99.999 Kcal/kg Integer R 14,15
I04a HUM_EXT Display of the outdoor air humidity 0.0 -99.9 99.9 %rH Analog. R 6
I04b ENTALPIA_INT_KCAL Display of the indoor enthalpy 0.0 -99.999 99.999 Kcal/kg Integer R 16,17
I04b HUM_INT Display of the indoor air humidity 0.0 -99.9 99.9 %rH Analog. R 5
I05a T_P_HP_C1 Display of the high pressure transducer of circuit 1 0.0 -99.9 99.9 bar Analog. R 3
I05a TEMP_CAL_HP_C1 Calculated temperature for high pressure of circuit 1 0.0 -99.9 99.9 °C Analog. R 123
I05a T_P_HP_C2 Display of the high pressure transducer of circuit 2 0.0 -99.9 99.9 bar Analog. R 4
I05a TEMP_CAL_HP_C2 Calculated temperature for high pressure of circuit 2 0.0 -99.9 99.9 °C Analog. R 124
INPUTS/OUTPUTS