13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of “Input/Output” (...continuation)
Screen Parameter Description of the parameter
Value Min. Max. UOM Type R/W
Add.
BMS
I05c T_P_LP_C1_AIN06 Display of the low pressure transducer of circuit 1 0.0 -99.9 99.9 bar Analog. R 204
I05c TEMP_CAL_LP_C1_AIN06 Calculated temperature for low pressure of circuit 1 0.0 -99.9 99.9 --- Analog. R 206
I05c T_P_LP_C2_AIN09 Display of the low pressure transducer of circuit 2 0.0 -99.9 99.9 bar Analog. R 205
I05c TEMP_CAL_LP_C2_AIN09 Calculated temperature for low pressure of circuit 2 0.0 -99.9 99.9 --- Analog. R 207
I05e TEMP_ASP_C1_AIN08 Display of the suction temperature of circuit 1 0.0 -99.9 99.9 --- Analog. R 251
I05e SHTemp_A Display of overheating of circuit 1 00.0 -99.9 99.9 --- Integer R
I05e TEMP_ASP_C2_AIN11 Display of the suction temperature of circuit 2 0.0 -99.9 99.9 --- Analog. R 252
I05e SHTemp_B Display of overheating of circuit 2 00.0 -99.9 99.9 --- Integer R
I05f TEMP_ASP_C2_AIN11 Display of the outdoor coil temperature (1-circuit units) 0.0 -99.9 99.9 --- Analog. R 252
I06a T_P_HP_C1 Display of the high pressure transducer of circuit 1 0.0 -99.9 99.9 bar Analog. R 3
I06a TEMP_CAL_HP_C1 Calculated temperature for high pressure of circuit 1 0.0 -99.9 99.9 °C Analog. R 123
I06a COMPRESOR_1 Contactor of compressor 1 circuit 1 0 0 1 --- Digital R 16
I06a COMPRESOR_1_2 Contactor of compressor 2 circuit 1 0 0 1 --- Digital R 76
I06a TEMP_ASP_C1_EVOS Suction temperature on circuit 1 0.0 -99.9 99.9 °C Analog. R
I06a T_P_LP_C1_EVOS Evaporating pressure on circuit 1 0.0 -99.9 99.9 bar Analog. R
I06a TEMP_CAL_LP_C1_EVOS Evaporating temperature on circuit 1 0.0 -99.9 99.9 °C Analog. R
I06a1 I4_EEV_POSITION_STEP Valve position (steps) of circuit 1 0 -9999 9999 --- Integer R
I06a1 A17_EEV_POSITION_PERCENT Valve opening (%) of circuit 1 0.0 0.0 100.0 % Analog. R 255
I06a1 EVD1_RegStatus Status of circuit 1 valve 0 -32768 32767 --- Integer R
I06a1 EVD1_ProtStatus Status of circuit 1 valve protection 0 -32768 32767 --- Integer R
I06a1 SH_A_EVOS Overheating on the expansion valve of circuit 1 0.0 -99.9 99.9 K Analog. R 253
I06b T_P_HP_C2 Display of the high pressure transducer of circuit 2 0.0 -99.9 99.9 bar Analog. R 4
I06b TEMP_CAL_HP_C2 Calculated temperature for high pressure of circuit 2 0.0 -99.9 99.9 °C Analog. R 124
I06b COMPRESOR_2 Contactor of compressor 1 circuit 2 0 0 1 --- Digital R 17
I06b COMPRESOR_2_2 Contactor of compressor 2 circuit 2 0 0 1 --- Digital R 77
I06b TEMP_ASP_C2_EVOS Suction temperature on circuit 2 0.0 -99.9 99.9 °C Analog. R
I06b1 T_P_LP_C2_EVOS Evaporating pressure on circuit 2 0.0 -99.9 99.9 bar Analog. R
I06b1 TEMP_CAL_LP_C2_EVOS Evaporating temperature on circuit 2 0.0 -99.9 99.9 °C Analog. R
I06b1 I149_EEV_POSITION_STEP_2ND Valve position (steps) of circuit 2 0 -9999 9999 --- Integer R
I06b1 A66_EEV_POSITION_PERCENT_2ND Valve opening (%) of circuit 2 0.0 0.0 100.0 % Analog. R 256
I06b1 EVD2_RegStatus Status of circuit 2 valve 0 -32768 32767 --- Integer R
I06b1 EVD2_ProtStatus Status of circuit 2 valve protection 0 -32768 32767 --- Integer R
I06b1 SH_B_EVOS Overheating on the expansion valve of circuit 1 0.0 -99.9 99.9 K Analog. R 254
I06c1 TEMP_ASP_C1_EVOS Suction temperature on circuit 1 0.0 -99.9 99.9 °C Analog. R
I06c1 SH_A_EVOS Overheating on the expansion valve of circuit 1 0.0 -99.9 99.9 K Analog. R 253
I06e T_P_LP_C1_EVOS Evaporating pressure on the circuit 1 valve 0.0 -99.9 99.9 bar Analog. R
I06e TEMP_CAL_LP_C1_EVOS Evaporating temperature on the circuit 1 valve 0.0 -99.9 99.9 °C Analog. R
I06f TEMP_ASP_C2_EVOS Suction temperature on circuit 2 0.0 -99.9 99.9 °C Analog. R
I06f SH_B_EVOS Overheating on the expansion valve of circuit 2 0.0 -99.9 99.9 K Analog. R 254
I06g T_P_LP_C2_EVOS Evaporating pressure on the circuit 2 valve 0.0 -99.9 99.9 bar Analog. R
I06g TEMP_CAL_LP_C2_EVOS Evaporating temperature on the circuit 2 valve 0.0 -99.9 99.9 °C Analog. R
I07 N_HOR_ON_EQUIPO Display of operating hours of unit 0 0 32767 h Integer R 62
I07 N_HOR_COMP1 Display of operating hours of compressor 1 circuit 1 0 0 32767 h Integer R 10
I07 N_HOR_COMP1_2 Display of operating hours of compressor 2 circuit 1 0 0 32767 h Integer R 53
I07a N_HOR_COMP2 Display of operating hours of compressor 1 circuit 2 0 0 32767 h Integer R 11
I07a N_HOR_COMP2_2 Display of operating hours of compressor 2 circuit 2 0 0 32767 h Integer R 69
I07a N_HOR_CR Display of operating hours of recovery compressor 0 0 32767 h Integer R 12
I08 DIN01_RTVI Status of digital input 1: supply fan thermal protection 0 0 1 --- Digital R 12
I08 DIN02_INC Status of digital input 2: gas detector 0 0 1 --- Digital R 135
I08 DIN03_AP1 Status of digital input 3: high pressure circuit 1 0 0 1 --- Digital R 1
I08 DIN04_TC1
Status of digital input 4: thermal protection of compressors and
outdoor fans of circuit 1
0 0 1 --- Digital R 5
I08 DIN05_TS_IC Status of digital input 5: safety of el. heaters / burner / boiler 0 0 1 --- Digital R 7
I08 DIN06_FS Status of digital input 6: clogged lters detector 0 0 1 --- Digital R 11
I08 DIN07_ON_OFF Status of digital input 7: remote ON/OFF 0 0 1 --- Digital R
I08 DIN08_AH_BAC_REC_ROT Status of digital input 8: antifreeze safety of the hot water coil (HWC) 0 0 1 --- Digital R
I08 DIN09_AP2 Status of digital input 9: high pressure circuit 2 0 0 1 --- Digital R 2
I08 DIN10_TC2
Status of digital input 10: thermal protection of compressors and
outdoor fans of circuit 2
0 0 1 --- Digital R 6
I08a DIN21_OFF_1ET Status of digital input 21: disconnection of 1 compressor stage 0 0 1 --- Digital R
I08a DIN_OFF_2ET Status of digital input 22: disconnection of 2 compressor stages 0 0 1 --- Digital R