13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of “Input/Output” (...continuation)
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
I08a DIN_OFF_4ET Status of digital input 23: disconnection of 4 compressor stages 0 0 1 --- Digital R
I08a DIN_OFF_RES Status of digital input 24: disconnection of electrical heaters 0 0 1 --- Digital R
I08b DIN25_DEBUG Status of digital input 25: opening of supply damper of zone 1 0 0 1 --- Digital R
I08b DIN26_DEBUG Status of digital input 26: opening of supply damper of zone 2 0 0 1 --- Digital R
I08b DIN27_DEBUG Status of digital input 27: opening of return damper of zone 1 0 0 1 --- Digital R
I08b DIN28_DEBUG Status of digital input 28: opening of return damper of zone 2 0 0 1 --- Digital R
I09 COMPRESOR_1 Status of contactor of compressor 1 circuit 1 0 0 1 --- Digital R 16
I09 COMPRESOR_1_2 Status of contactor of compressor 2 circuit 1 0 0 1 --- Digital R 76
I09 COMPRESOR_2 Status of contactor of compressor 1 circuit 2 0 0 1 --- Digital R 17
I09 COMPRESOR_2_2 Status of contactor of compressor 2 circuit 2 0 0 1 --- Digital R 77
I09a RES_ELECTRICA_1_O_VALV
Status of contactor of 1st stage of electrical heaters or gas burner or gas
boiler or hot water coil valve
0 0 1 --- Digital R 20
I09a RES_ELECTRICA_2 Status of contactor of 2nd stage of electrical heaters 0 0 1 --- Digital R 21
I10 OUT_VIC1 Status of cycle reversing valve of circuit 1 0 0 1 --- Digital R 18
I10 OUT_VIC2 Status of cycle reversing valve of circuit 2 0 0 1 --- Digital R 19
I10 VENTILADOR_EXT_1 Status of outdoor fan(s) of circuit 1 0 0 1 --- Digital R 23
I10 VENTILADOR_EXT_2 Status of outdoor fan(s) of circuit 2 0 0 1 --- Digital R 24
I10b DOUT18
Status of digital output 18: electical heating for the piping layout of the water
circuit with GREAT COLD or confi gurable output (humidifi er, HWC pump,
alarm signal,...)
0 0 1 --- Digital R
I10b DOUT19 Status of digital output 19: compressor with supplementary crankcase heater 0 0 1 --- Digital R
I10b DOUT20
Status salida digital 20: electrical heater for protection of fresh air damper
or solenoid valve SV1 with actve dehumidifi cation
0 0 1 --- Digital R
I10b DOUT21
Status of digital output 21: confi gurable output (humidifi er, HWC pump, alarm
signal,...) or solenoid valve SV2 with actve dehumidifi cation
0 0 1 --- Digital R
I10c DOUT22 Status of digital output 22: supply damper of zone 1 0 0 1 --- Digital R
I10c DOUT23 Status of digital output 23: supply damper of zone 2 0 0 1 --- Digital R
I10c DOUT24 Status of digital output 24: return damper of zone 1 0 0 1 --- Digital R
I10c DOUT25 Status of digital output 25: return damper of zone 2 0 0 1 --- Digital R
I11 ON_VENTILADOR_INT Status of indoor unit supply fan 0 0 1 --- Digital R 15
I11 OUT_07
Status of output NO7 in which one of the following options can be connected:
on-o humidifi er, circulation pump of the hot water coil, boiler pump, rotary
heat exchanger or remote alarm signal
0 0 1 --- Digital R
I12 AOUT_COMPUERTA
Display of opening % of fresh air damper (optional). Range vary between
0% (0V) and 100% (10V)
0.0 0.0 100.0 --- Analog. R 10
I12
AOUT_VALV_O_RES_
PROP_O_HUMIDIF
Display of opening % of : HWC heat valve or proportional electrical heater or
proportional humidifi er or gas burner/boiler or overpressure damper
0.0 0.0 100.0 --- Analog. R 11
I12a AOUT_VEN_EXT1 Display of operating % of electronic outdoor fan(s) of circuit 1 0.0 0.0 100.0 --- Analog. R 12
I12a AOUT_VEN_EXT2 Display of operating % of electronic outdoor fan(s) of circuit 2 0.0 0.0 100.0 --- Analog. R 13
I12b AOUT6
Display of % proportional humidifi er or exhaust damper or 3-way valve (3-WV)
of the condensation coil with active dehumidifi cation
0.0 0.0 100.0 --- Analog. R
I12c AOUT7
Display of operating % of the wheel (variable rotary heat exchanger) or
preheater with electrical heater
0.0 0.0 100.0 --- Analog. R
I12d SET_PRES_DIF_IMP Di erential pressure sensor setpoint for constant supply pressure 200 0 10000 Pa Integer R 292
I12d PRES_DIF_IMP Di erential pressure sensor reading for constant supply pressure 0 -99999 99999 Pa Integer R 291
I12e ACTIVAR_FBC1 Display of operation of the condensate pump 0 0 1 --- Digital R
I12e DEMANDA_ACTIVAR_FBC1 Condensate pump operating demand 0 0 1 --- Digital R
I15 VOLTAGE_L1_L2 Reading of the energy meter: voltage between phases L1-L2 0 -9999 9999 V Integer R 167
I15 VOLTAGE_L3_L1 Reading of the energy meter: voltage between phases L2-L3 0 -9999 9999 V Integer R 168
I15 VOLTAGE_L3_L1 Reading of the energy meter: voltage between phases L3-L1 0 -9999 9999 V Integer R 169
I15 VOLTAGE_L2 Reading of the energy meter: voltage between phase and neutral L1 0 -9999 9999 V Integer R 170
I15 VOLTAGE_L2 Reading of the energy meter: voltage between phase and neutral 2 0 -9999 9999 V Integer R 171
I15 VOLTAGE_L3 Reading of the energy meter: voltage between phase and neutral 3 0 -9999 9999 V Integer R 172
I16 CURRENT_L1 Reading of the energy meter: phase current L1 0.0 -999.9 999.9 A Analog. R 131
I16 CURRENT_L2 Reading of the energy meter: phase current L2 0.0 -999.9 999.9 A Analog. R 132
I16 CURRENT_L3 Reading of the energy meter: phase current L3 0.0 -999.9 999.9 A Analog. R 133
I16
TYPE_INDUCTIVE_O_
CAPACITIVE
Inductive character L (0) or capacitive character C (1) of the equivalent
electrical load of the unit
0 0 1 --- Digital R 334
I16 POWER_FACTOR Reading of the energy meter: power factor 0 0 32 --- Integer R 173
I16 FREQUENCY Reading of the energy meter: frequency 0.0 -999.9 999.9 Hz Analog. R 142
I17 REACTIVE_POWER_L1 Reading of the energy meter: reactive power phase L1 0.0 -999.9 999.9 kVAR Analog. R 134
I17 REACTIVE_POWER_L2 Reading of the energy meter: reactive power phase L2 0.0 -999.9 999.9 kVAR Analog. R 135
I17 REACTIVE_POWER_L3 Reading of the energy meter: reactive power phase L3 0.0 -999.9 999.9 kVAR Analog. R 136
INPUTS/OUTPUTS
E