13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of “Input/Output” (...continuation)
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
I08cr CR_DIN01_DEBUG Status of digital input: remote On/O 0 0 1 --- Digital R
I08cr CR_DIN02_DEBUG Status of digital input: high pressure switch of the recovery circuit 0 0 1 --- Digital R
I08cr CR_DIN03_DEBUG Status of digital input: compressor thermal protection of the recovery circuit 0 0 1 --- Digital R
I08cr DIN25_M8_C_F_DEBUG Status of digital input: remote Cooling/Heating 0 0 1 --- Digital R
I10cr COMPRESOR_REC Status of digital output: Contactor of the recovery compresor 0 0 1 --- Digital R 117
I10cr OUT_VIC_CR Status of digital output: cycle reversing valve of recovery compresor 0 0 1 --- Digital R 278
I10cr RELE_ALARMA_CR Status of digital output: alarm relay 0 0 1 --- Digital R
I10cr DOUT19 Status of digital output 19: compressor with supplementary crankcase heater 0 0 1 --- Digital R
I10cr DOUT20
Status of digital output 20: electrical heater for protection of fresh air damper or
solenoid valve SV1 with actve dehumidifi cation
0 0 1 --- Digital R
I10cr DOUT18
Status of digital output 18: electical heating for the piping layout of the water
circuit with GREAT COLD or confi gurable output (humidifi er, HWC pump,
alarm signal,...)
0 0 1 --- Digital R
I02zn TEMP_TCO11 Display of the temperature meaured by User terminal on zone 1 (air zoning) 0.0 -99.9 99.9 °C Analog. R 294
I02zn TEMP_TCO12 Display of the temperature meaured by User terminal on zone 2 (air zoning) 0.0 -99.9 99.9 °C Analog. R 295
I02zn TEMP_TCO13 Display of the temperature meaured by User terminal on zone 3 (air zoning) 0.0 -99.9 99.9 °C Analog. R 296
I02zn TEMP_TCO14 Display of the temperature meaured by User terminal on zone 4 (air zoning) 0.0 -99.9 99.9 °C Analog. R 297
I03zn TEMP_RET_Z1 Display of the NTC probe return temperature (optional) of zone 1 (air zoning) 0.0 -99.9 99.9 °C Analog. R 299
I03zn TEMP_RET_Z2 Display of the NTC probe return temperature (optional) of zone 2 (air zoning) 0.0 -99.9 99.9 °C Analog. R 300
I03zn TEMP_RET_Z3 Display of the NTC probe return temperature (optional) of zone 3 (air zoning) 0.0 -99.9 99.9 °C Analog. R 301
I03zn TEMP_RET_Z4 Display of the NTC probe return temperature (optional) of zone 4 (air zoning) 0.0 -99.9 99.9 °C Analog. R 302
I08zn
COMPUERTA_IMP_
ZONA1_ABIERTA
Status of digital input 01 of SMALL board (addr.11): air fl ow zoning 0 0 1 --- Digital R
I08zn
COMPUERTA_IMP_
ZONA2_ABIERTA
Status of digital input 02 of SMALL board (addr.11): air fl ow zoning 0 0 1 --- Digital R
I08zn
COMPUERTA_IMP_
ZONA3_ABIERTA
Status of digital input 03 of SMALL board (addr.11): air fl ow zoning 0 0 1 --- Digital R
I08zn
COMPUERTA_IMP_
ZONA4_ABIERTA
Status of digital input 04 of SMALL board (addr.11): air fl ow zoning 0 0 1 --- Digital R
I08zn
ZONIF_4Z_UPC2.
IN_DIG05_INC
Status of digital input 05 of SMALL board (addr.11): air fl ow zoning 0 0 1 --- Digital R
I08zn
ZONIF_4Z_UPC2.
IN_DIG06_RTVI
Status of digital input 06 of SMALL board (addr.11): air fl ow zoning 0 0 1 --- Digital R
I08zn
ZONIF_4Z_UPC2.
IN_DIG07_ON_OFF
Status of digital input 07 of SMALL board (addr.11): air fl ow zoning 0 0 1 --- Digital R
I09zn
COMPUERTA_IMP_
ZONA1_ABIERTA
Status of supply damper of zone 1 (air fl ow zoning) 0 0 1 --- Digital R
I09zn
COMPUERTA_IMP_
ZONA2_ABIERTA
Status of supply damper of zone 2 (air fl ow zoning) 0 0 1 --- Digital R
I09zn
COMPUERTA_IMP_
ZONA3_ABIERTA
Status of supply damper of zone 3 (air fl ow zoning) 0 0 1 --- Digital R
I09zn
COMPUERTA_IMP_
ZONA4_ABIERTA
Status of supply damper of zone 4 (air fl ow zoning) 0 0 1 --- Digital R
I09zn ZONIF_4Z_UPC2.DOUT5 Status of output No.5 of SMALL board (addr.11) (air fl ow zoning) 0 0 1 --- Digital R
I09zn ZONIF_4Z_UPC2.DOUT6 Status of output No.6 of SMALL board (addr.11) (air fl ow zoning) 0 0 1 --- Digital R
I09zn
ZONIF_4Z_UPC2.RELE_
ALARMA_4Z
Status of alarm relay of SMALL board (addr.11) (air fl ow zoning) 0 0 1 --- Digital R
I19
A2L_SENSOR_
PERCENT_LFL
Percentage LFL of A2L sensor (leak detector R-454B) 0.0 -999.9 999.9 % Analog. R 316
I19
A2L_SENSOR_
PERCENT_VOL
Volume percentage of A2L sensor (R-454B leak detector) 0.0 -999.9 999.9 % Analog. R 317
I19 A2L_SENSOR_TEMP A2L sensor temperature (R-454B leak detector) 0.0 -999.9 999.9 °C Analog. R 318
I19 A2L_SENSOR_LIFE A2L Sensor Life (R-454B leak detector) 0 0 32767 --- Integer R 293
Parameters of “Access Levels”
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
NA01 ACTUAL_ACCES_LEVEL Current access level 1 1 9 --- Integer R
NA01 NOT_PASS_ACCESS_LEVEL_1 Without access to level 1 0 0 1 --- Digital R/W
NA01 MASK_ACCES_LEVEL_1 Access to level 1 0 0 1 --- Digital R/W
NA01 NOT_PASS_ACCESS_LEVEL_2 Without access to level 2 0 0 1 --- Digital R/W
NA01 MASK_ACCES_LEVEL_2 Access to level 2 0 0 1 --- Digital R/W
NA01 NOT_PASS_ACCESS_LEVEL_3 Without access to level 3 0 0 1 --- Digital R/W
NA01 MASK_ACCES_LEVEL_3 Access to level 3 0 0 1 --- Digital R/W