Parameters of “Versions”
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
V01 logo_bool Type of logo 0 0 1 --- Digital R/W
V01 PROJECT_RELEASE_1 Release version 0 0 9 --- Analog. R
V01 DIA_COMPILACION Software version compilation day 0 1 31 --- Integer R
V01 MES_COMPILACION Software release build month 0 1 12 --- Integer R
V01 ANO_COMPILACION Software release compilation year 0 0 99 --- Integer R
V01 OsVersion Board operating system version 0 0 999 --- Integer R
V01 BootVersion Boot version 0 0 999 --- Integer R
V02 BoardTyp[1] Board Type (PC3) 0 0 99 --- Integer R
V02 BoardTyp[2] Board size (Medium) 0 0 99 --- Integer R
V02 PrgCycleMs Program cycle in ms 0 0 9999 --- Integer R
V02 CyclesPerSecond Program cycles per second 0 -99999.9 99999.9 --- Analog. R
13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of “Alarms History”
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
H01 AlrmLogsIdx Index to sort alarms 0 0 999 --- Integer R
H01 AlrmLogHour Time to which the alarm log value is referred by the AlrmLogsIdx index 0 0 99 --- Integer R
H01 AlrmLogMinute Minute to which the alarm log value is referred by the AlrmLogsIdx index 0 0 99 --- Integer R
H01 AlrmLogDay Day to which the alarm log value refers by the AlrmLogsIdx index 0 0 99 --- Integer R
H01 AlrmLogMonth Month to which the alarm log value refers by the AlrmLogsIdx index 0 0 99 --- Integer R
H01 AlrmLogYear Year to which the alarm log value refers by the AlrmLogsIdx index 0 0 99 --- Integer R
H01 AlrmLogCode Alarm code (used to display active alarms from the alarm table) 0 0 9 --- Integer R
H02 AlrmLogDelete
Clear alarm log (0: Nothing 1: Clear alarm log)
NOTE: Required to be at level 3 access
0 0 1 --- Digital R/W
Parameters of “Burner/Boiler”
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
G01 CONTROL_QUEMADOR_GAS
Control of the gas burner or gas boiler:
0 = burner/boiler as 2nd stage;
1 = only burner/boiler
2 = only burner/boiler with low outdoor temperature
0 0 2 --- Integer R/W 2
G01 SET_QUEMADOR_BAJA_TEXT
Setpoint of outdoor temperature below which the burner/boiler is activated
instead of compressors
5.0 -10.0 10.0 °C Analog. R/W 120
ALARMS
M
CRTL_ID
O
GASCONFIG
D