15 - TECHNICAL AND ELECTRICAL CHARACTERISTICS
c.pCOe expansion modules
TECHNICAL CHARACTERISTICS
Storage conditions -40T70 ºC; %HR 90 non-condensing
Operating conditions -20T70 ºC; %HR 90 non-condensing
Protection index IP40 only on the front panel
Environmental pollution Level 3
Classi cation according to protection against electric shocks To be incorporated in class I and/or II appliances
Period of electric stress across the insulating parts Long
Type of relay action 1C
Type of disconnection or microswitching Micro-switch for all of the relay outlets
Category of resistance to heat and re Category D
Immunity from voltage surge Category III
Software class and structure Class A
Dimensions: Length x height x width
110 x 70 x 60 mm (4 DIN modules)
ELECTRICAL CHARACTERISTICS
Power supply 24 Vca +10/-15% 50/60 Hz, 28 to 36 Vdc +10/-15%, 15 VA / 6 W
Basic model maximum power consumption 15 VA / 6 W
Enhanced model maximum power consumption 30 VA / 12 W
Maximum connector voltage (NO1…C6) 250 Vac
Meaning of the LEDs
Yellow LED
ashing when setting the address (setting the o󰀨 set);
on in the event of incorrect address setting
Green LED ashing if BMS port communication online, on steady if o󰀪 ine.
Universal channels
Number 10
Analogue / digital conversion 14 bits
Type of input selectable
NTC, PT1000, PT500, PT100, 4 to 20 mA, 0 to 1 V, 0 to 5 V, 0 to 10 V, 0 to 2 kHz (resolution
±1Hz) on/o󰀨 or open collector digital input (2 kOhm)
Type of output selectable PWM 0/3.3 V 100 Hz, PWM 0/3.3 V, 2 mA 2 kHz, 0 to 10 V analogue output
Maximum current output 2 mA
Precision of analogue input reading ± 0,3% of full scale
Analogue output precision ± 2% of full scale
Digital outputs
Number 6
Group 1 (R1, R2); Group 2 (R3, R4, R5)
2(1) A (100,000 cycles); UL60730: 5 A resistive, 250 Vac, 30k cycles, 105°C,De ned Purpose,
1FLA, 6LRA, 250 Vac, 30k cycles, 105°C, pilot duty C300, 250 Vac, 30k cycles, 105°C.
Group 3 (R6)
1(1) A (100,000 cycles) Maximum switchable voltage: 250 Vac; UL 60730-1: 1 A resistive, 1 A
FLA, 6 A LRA, 250 Vac, D300 pilot duty, 30,000 cycles.
Single-pole valve output (Enhanced model only)
Number / type 1 / single-pole
Maximum output 8 W
Connector 6-pin, xed sequence
Power supply 13 Vdc ±5%
Maximum current: 0.35 A for each winding
Minimum winding resistance 40