9
5 - HANDLING
Detail A
Expander
Sling
Stretcher
3700 min
See detail A
Detail A
Expander
Sling
A B
C
3000
3700 min
A B
C
D
3000
See detail A
50FF/FC Assemblies Confi guration
No. riggings
points x
beam
Unit
width
(mm)
Beam
length
(mm)
Distance between riggings points
(mm)
ABCD
020 / 028 B1, B2, BF, B3, BX, BP, BA, BT, BB, BW 1 2 1750 2215 300 1600 315 -
037 / 040 / 045 / 047 B1, B2, BF, B3, BX, BP, BA, BT, BB, BW 2 2 1750 2215 300 1600 315 -
052 / 058 / 062 B1, B2, BF, B3, BX, BP, BT, BW 3 2 2200 2985 732,5 1520 732,5 -
052 / 058 / 062 R1, R2, RP, RW 4 2 2200 2985 732,5 1520 732,5 -
052 / 058 / 062 BA, BB 5 3 2200 2985 732,5 665 855 732,5
070 / 074 / 086 / 093 B1, B2, BF, B3, BX, BP, BT, BW 6 2 2200 3639 779,5 2130 729,5 -
070 / 074 / 086 / 093 R1, R2, RP, RW 7 2 2200 3639 779,5 2130 729,5 -
070 / 074 / 086 / 093 BA, BB 8 3 2200 3639 779,5 995 1135 729,5
Confi gurations 1, 2, 3, 4, 6 and 7
Confi gurations 5 and 8
After the placing of the unit, it is recommended to remove the grips as they can be a hindrance for maintenance. The grips are fi xed
to the beams using M10 screws (hex. key 17). Put the grips back in case of unit transport (tightening torque of screws 25 Nm).
Important: The centre of gravity is not necessarily in the middle of the unit and the forces applied to the slings are not always identical.
Please consult the weight and the centre of gravity of each model stated in paragraph 7.6.
Important: all rigging points must be used