• Forced:
Manual:
3 setpoints schedule + OFF of unit:
Disab.comp.COOL:
Dis. air refresh.:
PH03
Start type
'Manual'
ON
PH03
Start type
3 setpoints schedule
+ OFF of unit
- ON for SET LIMITE -
Disab. comp. COOL: N
Dis. air refresh.: N
PH03
Start type
-FORCED-
ON time: 002 h
PH11
Schedule with ON
by limit SP
Win.Lim. Diff.01.0ßC
Sum.Lim. Diff.02.0ßC
-
PH13
MON copy to TUE: YES
23:00 to 23:30
00-08:
----------
08-16:
16-24:
--
PH14
Schedule with setpoint
change (Summer)
CONFORT Set 26.0ßC
ECONOMY Set 28.0ßC
PROTECTION Set 34.0ßC
PROT.Lim.Dif 02.0ßC
Set.CONFORT:
Set.ECONOMY:
Set.PROTECTION:
Dif.lim.PROT:
PH15
Schedule with setpoint
change (Winter)
CONFORT Set 21.0ßC
ECONOMY Set 19.0ßC
PROTECTION Set 13.0ßC
PROT.Lim.Dif 01.0ßC
9 - SCHEDULE PROGRAMMING
PH03
Start type
'Manual'
OFF
PH10
Schedule with ON
by limit SP (winter)
Indoor set. 21.0ßC
Limit set. 13.0ßC