7 - POSITIONING AND INSTALLATION
7.6 - Recommended service clearance
Important: This is the minimum space required for maintenance operations and access inside the unit. Depending on the assembly
selected for the unit and the characteristics of the installation site, a larger space around it may be required to ensure proper air
circulation and therefore the correct operation of the unit.
Unit not designed to have overhead obstruction.
50FF/FC - 180 to 280
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height A B C D
180 to 220 5.300 2.257 2.421 2.600 2.500 1.200 1.000
250 to 280 6.350 2.257 2.494 3.000 2.500 1.200 1.000
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height A B C D
180 to 220 5.300 2.257 2.555 2.600 2.500 1.200 1.000
250 to 280 6.350 2.257 2.555 3.000 2.500 1.200 1.000
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height A B C D
180 to 220 5.300 3.112 2.555 2.600 1.700 1.200 1.000
250 to 280 6.350 3.112 2.555 3.000 2.500 1.200 1.000
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height A B C D
180 to 220 5.306 2.268 2.555 2.600 2.500 1.200 1.000
250 to 280 6.356 2.268 2.555 3.000 2.500 1.200 1.000