APPENDIX A — LOCAL DISPLAY AND CCN TABLES
MODE — OPERATING MODES
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN
WRITE
STATUS
DISPLA Y
WRITE
STA TUS
OPERATING MODES MAINTENANCE
DISPLAY
MODE Control Modes MODES
SYS Unit operation disabled
Unit operation enabled
Service test enabled
SYS_MODE_TEXT1
SYS_MODE_TEXT2
(table only)
SYS_MODE_TEXT3
table only)
HVAC HVAC Operation Disabled
Ventilation (fan--- only)
Cooling
Free Cooling
Unoccupied Free Cooling
Reheat1
Reheat2
Reheat1 / Reheat2
Heating
HVACMODE_TEXT_1
HVACMODE_TEXT_2
(table only)
HVACMODE_TEXT_3
(table only)
F. M O D Indoor Fan Mode x IDF_MODE
F. O V R Fan Override in Effect No/Yes FAN_OVR
HV.DN Remote HVAC Mode Disable No/Yes HVACDOWN forcible
EFF.C Cool Setpoint In Effect xx.x _F CSP_EFF
EFF.H Heat Setpoint In Effect xx.x _F HSP_EFF
OCC Currently Occupied No/Yes OCCUPIED forcible forcible
T. O V R Timed Override in Effect No/Yes MODETOVR
LINK Linkage Active No/Yes MODELINK
D.LMT Demand Limit In Effect No/Y es MODEDMDL
C.LOC Compressor OAT Lockout No/Y es COMPLOCK
H.LOC Heat OAT Lockout No/Yes HEATLOCK
OK.EC OK to Use Economizer? No/Y es ECONCOOL
COOL Cool Mode Diagnostic COOLDIAG
COOL In Cooling Mode? No/Yes IN_COOL
OK.CL OK to Select Cool Mode? No/Yes OKTOCOOL
MS.TG Mode Select Timeguard xxx secs COOLMSTG
OK.EC OK to Use Economizer? No/Y es ECONCOOL
OK.MC OK to Use Compressors? No/Y es MECHCOOL
C.LOC Compressor OAT Lockout No/Y es COMPLOCK
CA.LO CircuitALockoutTemp xxx _F OATLCMPA
CB.LO CircuitBLockoutTemp xxx _F OATLCMPB
F. M O D Indoor Fan Mode x IDF_MODE
F.SPD Commanded Fa n Speed NNN % FANSPEED
AVL.C Available Cooling Stages x AVLCSTGS
REQ.C Requested Cooling Stages x REQCSTGS
LMT.C Max Cool Stage In Effect x CSTGLIMT
ACT.C Actual Cooling Stages x ACTCSTGS
CMP.A Circuit A Compressor(s) Off/On COMP_A
CMP.B Circuit B Compressor Off/On COMP_B
ST.A Circuit A Strikes x ASTRIKES
ST.B Circuit B Strikes x BSTRIKES
HPS.A Ckt A Hi Pres Sq Check No/Yes INHPSCKA
HPS.B Ckt B Hi Pres Sq Check No/Y es INHPSCKB
SAT Supply Air Temperature
SAT Supply Air Temperature xxx.x _F SAT_DISP
SA.DM Supply Air Temp Demand xxx.x ^F SAT_DMD
SA.PD SAT Cool Demand (+) Level xx.x ^F SAT_POS
SA.ND SAT Cool Demand (--- ) Level xx.x ^F SAT_NEG
SAT.U Minimum SAT Upper Level xx.x _F SATMIN_H
SAT.L Minimum SAT Lower Level xx.x _F SATMIN_L
SA.TR Supply Air d/dt (F/min) xxxx.x SATTREND
SA.DR SAT Delta Reference Temp xxx.x _F SAT_REF
SPT Space Temperature
SPT Space Temperature xxx.x _F SPACE_T forcible forcible
DMD.C Cooling Demand xxx.x ^F COOL_DMD
TRD.C Cool Demand d/dt (F/min) xxx.x CLDTREND
CL.PD SPT Cool Demand (+) Level xx.x ^F DEM_POS
CL.ND SPT Cool Demand ( --- ) Level xx.x ^F DEM_NEG
C.LAG Cool Thermal Lag Factor x.x COOL_LAG COOL _LAG
HMZR Humidimizer
REHT Humidimizer Equipped No/Yes REHEAT
HUM Space Humidity Switch Low/High HUM_STAT forcible
SP.RH Space Humidity Sensor xxx.x % SPRH forcible forcible
R.LO.A Reheat2 OAT Lockout A No/Yes RHALOCK
RA.LO Reheat2 OAT Limit A xx _F OATLRH_A
R.LP.A Reheat2 SSP Override A No/Y es RHALPOV
R.LO.B Reheat2 OAT Lockout B No/Yes RHBLOCK
RB.LO Reheat2 OAT Limit B xx _F OATLRH_ B