14
DETAIL “A”
PLACE ALL SEAL STRIP IN PLACE
BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
SEE DETAIL “A”
“C”
“B”
“A”
914-1371
(36"-54")
SPREADER
BARS
REQUIRED
C10410
UNIT
MAX WEIGHT
DIMENSIONS
A B C
LB KG IN MM IN MM IN MM
50HCQA,D07 1100 500 88.0 2235 40.8 1035 41.5 1055
50HCQD08 1315 598 88.0 2235 41.6 1057 49.5 1257
50HCQD09 1505 684 88.0 2235 40.0 1015 49.5 1257
NOTES:
1. SPREADER BARS REQUIRED to lift and transport the unit. Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered
around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
Fig. 9 − Rigging Details
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit
without factory−installed economizer or return air smoke
detector option may be field−converted to horizontal
ducted configuration. To convert to horizontal
configuration, remove screws from side duct opening
covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation−side
down. Seals around duct openings must be tight. See
Fig. 10.
Field−supplied flanges should be attached to horizontal
duct openings and all ductwork should be secured to the
flanges. Insulate and weatherproof all external ductwork,
joints, and roof or building openings with counter flashing
and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when insulating horizontal ductwork.
C06108
Fig. 10 − Horizontal Conversion Panels
50HCQ