EasyManua.ls Logo

Carrier 50HJ009 - Field Control Wiring; Field Control Wiring Raceway; Low Voltage Connections; Low-Voltage Connections

Carrier 50HJ009
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
FIELD CONTROL WIRING Install a Carrier-approved
accessory thermostat assembly according to installation
instructions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense aver-
age temperature in accordance with thermostat installation
instructions.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals to low-voltage connections on
unit (shown in Fig. 9A or 9B) as described in Steps 1 through 4
below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice at the
thermostat.
1. If mounted on a roof curb and electrical power is to be
run through the basepan, an accessory thru-the-bottom
connection kit is required. This is available through the
local Carrier distributor. This kit is required to ensure a
reliable water-tight connection.
2. If unit is mounted on roof curb and accessory thru-the-
bottom service connections are used, route wire through
connections.
3. Pass control wires through the hole provided on unit (see
connection D in Connection Sizes table in Fig. 7).
4. Feed wire through the raceway built into the corner post
to the 24-v barrier located on the left side of the control
box. See Fig. 10. The raceway provides the UL required
clearance between the high-voltage and low-voltage
wiring.
5. Connect thermostat wires to screw terminals of low-
voltage connector (see Fig. 9A or 9B).
NOTE: If thru-the-bottom power connections are used refer to
the accessory installation instructions for information on power
wiring. Refer to Fig. 7 for drilling holes in basepan.
HEAT ANTICIPATOR SETTINGS For units with electric
heat, set heat anticipator settings as shown in Table 4.
W2
C
Y1
G
R
Y2
W1
C
G
R
Y2
W1
X
W2
C
Y1
G
R
Y2
W1
X
24 VAC
RMTOCC
CMPSAFE
FSD
NOT USED
C
X
SFS
THERMOSTAT CONTROL
CONNECTION
BOARD
BOARD
CONNECTION
CONTROL
Fig. 9B Low Voltage Connections
(Units with PremierLink™ Controls)
CONNECTION
BOARD
FACTORY-
INSTALLED
DISCONNECT
(OPTION)
RACEWAY
COMPRESSOR
NO. 2
COMPRESSOR
NO. 1
CONVENIENCE
OUTLET
(OPTION)
HOLE IN
END
PANEL
Fig. 10 Field Control Wiring Raceway
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
(CONNECTION
BOARD)
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
THERMOSTAT DIPSWITCH SETTINGS
R
G
Y1
Y2
W1
W2
C
IPD/X
ON
OFF
A
B
C
D
LEGEND
NOTE: Underlined letter indicates active thermostat output when
configured for A/C operation.
Fig. 9A Low-Voltage Connections
(Standard Controls)
Field Wiring

Table of Contents

Related product manuals